DECISION
FILE NO.: 040126
LOCATION OF PREMISES: 845 Oaklawn Avenue
APPLICANT: Mr. Rick Colardo, Jr. Applegate Realty Co. Inc. 1481 Atwood Avenue Johnston, RI 02919
USE OR OCCUPANCY: Mixed
DATE OF DECISION: 2005-02-11
The above-captioned case was scheduled for hearing on November 9, 2004 at 1:00 P.M.  At that time, Chairman Farrell and Commissioners Preiss, Newbrook, Pearson, Burlingame, Coutu and Filippi were present.  The fire service was represented by Assistant Deputy State Fire Marshal Timothy Hawthorne of the Cranston Fire Marshal’s Office.  A motion was made by Commissioner Burlingame and seconded by Commissioner Pearson to grant the Applicant relief as outlined herein.  The motion was unanimous.

FINDINGS OF FACT
	
The numbers of the Decision below correspond with those of a February 12, 2004 inspection report compiled by the Cranston Fire Marshal’s Office.  The above report was utilized by the Board, the Applicant and the Cranston Fire Marshal’s Office during the November 9, 2004 hearing on this matter.  Accordingly, the Board hereby incorporates the February 12, 2004 inspection report as its initial findings of fact.  Any modification of the Board’s findings, such as correction of a deficiency by the Applicant, shall be noted herein. 
	
Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Applicant.  The term “approved”, as used herein, is understood to mean “in accordance with the specific provisions related to the particular subject as are contained in the State Fire Code, or as approved in particular by the authority having jurisdiction (the State Fire Marshal or his or her designated Deputy State Fire Marshal or Assistant Deputy State Fire Marshal)”.

CONCLUSIONS AND VARIANCE REQUESTS
	
1.  It is the understanding of the Board that the Applicant shall correct deficiency #1 at the direction and to the satisfaction of the Cranston Fire Marshal’s office.
	
2.  The Board hereby grants a variance from the provisions of section 13.1.6 in order to allow the Applicant to not sprinkler the basement portion of this facility provided that the basement be limited only to business occupancy at the direction and to the satisfaction of the Cranston Fire Marshal’s office.
	
3. through 10.  It is the understanding of the Board that the Applicant shall correct deficiencies 3, 4, 5, 6, 7, 8, 9 and 10 at the direction and to the satisfaction of the Cranston Fire Marshal’s office.
	
11.  The Board hereby grants a variance from the provisions of section 7.2.2.5.3 in order to allow the Applicant to maintain the unenclosed electrical room under a metal stairwell within this facility.  In granting this variance, the Board directs the Applicant to provide this area with an approved domestically supplied sprinkler head installed at the direction and to the satisfaction of and within a timetable established by the Cranston Fire Marshal’s office.  In granting this variance, it is the understanding of the Board that this stairway services only the lower level of this facility.

STATUS OF DECISION AND APPEAL RIGHTS
	
This Decision represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicant’s timely and continued compliance with all of the directives of the Board.  Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board. (See:  Board Rules and Regulations, section 6-2-17).
	
Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  (See: Board Rules and Regulations, section 6-2-18.)  In the event of complete, timely and continued compliance with the full Decision of the Board, the above cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the Fire Code or a revision of the above-cited classification.  (See: Board Rules and Regulations, section 6-2-19).  

Such changes in use or occupancy of this facility, or failure to continually comply with the Board’s Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in R.I.G.L. 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.  (See: Board Rules and Regulations, section 6-2-20).
	
The Applicant may appeal the Board’s Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth division of the District Court.  Commencement of such an action does not operate as an automatic stay of this Decision [R.I.G.L. 42-35-15(c)].