DECISION
FILE NO.: 020046
LOCATION OF PREMISES: 151 Park Street
APPLICANT: Mr. Manuel Florez 124 Boutwell Street Pawtucket, RI 02860
USE OR OCCUPANCY: Apartment
DATE OF DECISION: 2003-02-04
	The above captioned case was scheduled for a hearing on March l9, 2002 at l:00  p.m.  At that time, Acting Chairman Coutu and Commissioners Newbrook, O’Connell, Richard and Evans were present. The fire service was represented by Assistant Deputy State Fire Marshal Jeffrey Johnson of the Pawtucket Fire Marshal’s Office.  A motion was made by Commissioner Newbrook and seconded by Commissioner Evans to recommend the requested relief.  The motion was unanimous.
	
FINDING OF FACT

The numbers of the Decision below correspond with those of a January 23, 2002 inspection report compiled by the Pawtucket Fire Marshal’s Office.  The above report was utilized by the Board, the Applicant and the Pawtucket Fire Marshal’s Office during the March l9, 2002 hearing on this matter.  Accordingly, the Board hereby incorporates the January 23, 2002 inspection report as its initial findings of fact.

	Any deficiency, understood by the Board, to have been corrected which is not so corrected shall be immediately corrected by the Applicant.  The term approved as used 
herein is defined in Section 23-28.l-4(3) of the Rhode Island General Laws.

CONCLUSIONS AND VARIANCE REQUESTS

1.	The Board hereby grants the Applicant a variance from the provisions of Section 23-28.l6-2 in order to allow the Applicant to maintain the existing egress system of this facility as modified herein. 

2.	The Board hereby grants the Applicant a variance from the provisions of Section 23-28.l6-3 in order to allow the Applicant to maintain the current kitchen access to the egress system along with the existing fire escape system including the existing lead to ground from the fire escape ladder.  As a condition of this variance, the Board hereby directs the Applicant to change the undersized window leading to the fire escape from the third floor apartment, at the direction and to the satisfaction of the Pawtucket Fire Marshal before occupancy of this facility.

3.	The Board hereby grants the Applicant a variance from the provisions of Section 23-28.l6-5 in order to allow the Applicant to maintain the existing cited rating of the stairway within this facility.  It is the understanding of the Board that the Applicant has already applied an approved Class “A” finish located in the stairway of this facility.

4.	The Board hereby grants the Applicant a variance from the provisions of Section 23-28.l6-6 in order to allow the Applicant to provide the existing apartment door jambs of this facility with approved solid core wood doors maintaining an approximate fire rating of twenty (20) minutes.  The above doors shall be further equipped with spring-loaded hinges, and installed at the direction and to the satisfaction of the Pawtucket Fire Marshal, before occupancy of this facility.  Finally, the Board directs the Applicant to reswing the front door of this facility within thirty (30) days or before reoccupancy of this facility.

5.	The Board hereby directs the Applicant to correct deficiency #5 by providing this facility with approved fire stopping, installed at the direction and to the satisfaction of the Pawtucket Fire Marshal, before occupancy.

6.	As a condition of the variances granted herein, the Board hereby directs the Applicant to provide one (l) exit sign over the main egress door of this facility.  The above sign shall be installed at the direction and to the satisfaction of the Pawtucket Fire Marshal before occupancy.

7.	As a condition of the variances granted herein, the Board hereby directs the Applicant to provide this facility with approved emergency lighting, installed at the direction and to the satisfaction of the Pawtucket Fire Marshal, in accordance with the provisions of Section 23-28.l6-12, before occupancy of this facility.

8.	The Board hereby grants a variance from the provisions of Section 23-28.l6-l3 and NFPA Standard l0, l988 edition in order to allow the Applicant to provide each of the apartment units with an approved fire extinguisher, installed at the direction and to the satisfaction of the Pawtucket Fire Marshal.  It is the understanding of the Board that the above extinguishers are already installed.

9.	As a condition of the variances granted herein, the Board directs the Applicant to provide this facility with an approved fire alarm system, installed at the direction and to the satisfaction of the Pawtucket Fire Marshal or designee, in accordance with the provisions of Section 23-28.25-4(a), installed at the direction and to the satisfaction of the Pawtucket Fire Marshal, before occupancy.

This Decision represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicant’s timely and continued compliance with all of the directives of the Board.  Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board.

Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  In the event of complete, timely and continued compliance with the full Decision of the Board, the above-cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the Fire Code or a revision of the above-cited classification.  Such changes in use or occupancy of this facility, or failure to continually comply with the Board’s Decision, shall void all variances granted under the above-cited use or occupancy.  If such changes creates a new use or occupancy as outlined in R.I.G.L. 23-28.l-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.

	The Applicant may appeal the Board’s Decision within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth Division of the District Court.  Commencement of such an action does not operate as an automatic stay of this Decision.  [RIGL 42-35-l5(c)]