DECISION
FILE NO.: 100128
LOCATION OF PREMISES: 735 New London Avenue
APPLICANT: Mr. Joseph Costanzo Facilities and Operations 300 New London Avenue cranston, RI 02920
USE OR OCCUPANCY: Other
DATE OF DECISION: 2010-12-23
The above-captioned case was scheduled for hearing on October 5, 2010 at 1:00 P.M.  At that time, Acting Chairman Newbrook and Commissioners Blackburn, Filippi, Dias, Richard and Preiss were present.  The fire service was represented by Deputy State Fire Marshal Cynthia Dealer of the State Fire Marshals Office.  A motion was made by Commissioner Blackburn and seconded by Commissioner Filippi to grant the Applicant relief as outlined herein.  The motion was unanimous.

FINDINGS OF FACT
	The numbers of the Decision below correspond in sequence with those of a May 24, 2010 inspection report compiled by the State Fire Marshals Office.  The above report was utilized by the Board, the Applicant and the State Fire Marshals Office during the October 5, 2010 hearing on this matter.  Accordingly, the Board hereby incorporates the May 24, 2010 inspection report as its initial findings of fact.  Any modification of the Boards findings, such as correction of a deficiency by the Applicant, shall be noted herein. 

Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Applicant.  The term approved, as used herein, is understood to mean in accordance with the specific provisions related to the particular subject as are contained in this Code, or as approved in particular by the State Fire Marshal or his or her designee.

CONCLUSIONS AND VARIANCE REQUESTS 
	1.  (10-1176-VN)  It is the understanding of the Board that the Applicant has corrected deficiency 1 by properly testing the fire alarm system within this facility.
	2.  (10-1179-VN)  It is the understanding of the Board that the Applicant has corrected deficiency 2 by replacing the cited dryer vent hose within this facility.
	3.  (10-1177-VN)  It is the understanding of the Board that the Applicant has corrected deficiency 3 by properly protecting and locking the fire alarm circuit breaker within the boiler room of this facility.
	4.  (10-1180-VN)  The Board hereby grants the Applicant a time variance until December 31, 2010 in which to submit plans for the sprinkler system of this facility to the State Fire Marshals Office.  The Board further grants the Applicant an additional time variance until December 31, 2011 in order to implement the plans by providing this facility with an approved sprinkler system.
	5.  (10-1178-VN)  It is the understanding of the Board that the Applicant has corrected deficiency 5 by properly mounting the cited fire extinguisher located in the staff office of this facility.

STATUS OF DECISION AND APPEAL RIGHTS
	This Decision represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicants timely and continued compliance with all of the directives of the Board. Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board.  (See: Board Rules and Regulations, section 6-2-17).
	Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  (See: Board Rules and Regulations, section 6-2-18.)  In the event of complete, timely and continued compliance with the full Decision of the Board, the above cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the Fire Code or a revision of the above-cited classification.  (See: Board Rules and Regulations, section 6-2-19). 
 
Such changes in use or occupancy of this facility, or failure to continually comply with the Boards Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in R.I.G.L. 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.  (See: Board Rules and Regulations, section 6-2-20).
	The Applicant may appeal the Boards Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth division of the District Court.  Commencement of such an action does not operate as an automatic stay of this Decision [R.I.G.L. 42-35-15(c)].