Fire Safety Code, Rhode Island

Decisions - Details

STATE OF RHODE ISLAND
(401) 889-5551 phone
(401) 889-5279 fax
711 TTY
FIRE SAFETY CODE - BOARD OF APPEAL AND REVIEW
560 Jefferson Boulevard
Suite 202
Warwick, RI 02886
DECISION
FILE NO.: 080325
LOCATION OF PREMISES: 1 Talbot Street
APPLICANT: Talbot Realty LLC 18 Reade Stree North Providence, RI 02904
USE OR OCCUPANCY: Apartment
DATE OF DECISION: 2011-05-27
The above-captioned case was scheduled for hearing on March 15, 2011 at 1:00 P.M.  At that time, Chairman Newbrook and Commissioners Dias, Filippi, Pearson, Walker, Jasparro, Preiss and Blackburn were present.  The fire service was represented by Assistant Deputy State Fire Marshals Gregory Unsworth and John Horan of the North Providence Fire Marshals Office.  A motion was made by Commissioner Pearson and seconded by Commissioner Filippi to grant the Applicant relief as outlined herein.  The motion was unanimous.

FINDINGS OF FACT
	The numbers of the Decision below correspond with those of an October 17, 2008 inspection report compiled by the North Providence Fire Marshals Office.  The above report was utilized by the Board, the Applicant and the North Providence Fire Marshals Office during the March 15, 2011 hearing on this matter.  Accordingly, the Board hereby incorporates the October 17, 2008 inspection report as its initial findings of fact.  Any modification of the Boards findings, such as correction of a deficiency by the Applicant, shall be noted herein. 

Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Applicant.  The term approved, as used herein, is understood to mean in accordance with the specific provisions related to the particular subject as are contained in this Code, or as approved in particular by the State Fire Marshal or his or her designee.

CONCLUSIONS AND VARIANCE REQUESTS 
	1.  The Board hereby grants the Applicant a time variance of thirty (30) days from the date of this decision in which to develop and submit a plan of action for the upgrade of the fire alarm system within this facility and an additional 120 days in order to implement that plan of action at the direction and to the satisfaction of the North Providence Fire Marshals Office.  The Board notes that the North Providence Fire Marshals Office shall be allowed to extend either or both of the above timelines for good faith efforts being shown by the Applicant.
	2-3.  The Board hereby directs the Applicant to correct deficiencies 2 and 3 within the time lines outlined in item 1 above.
	4.  It is the understanding of the Board that the Applicant has corrected deficiency 4 by sealing the penetrations in the boiler room.
	5.  The Board hereby directs the Applicant to correct deficiency 5 within the timetable outlined in item 1 above.
	6.  The Board hereby grants the Applicant a time variance of thirty days from the date of this decision in which to correct deficiency 6 by providing this facility with approved portable fire extinguishers.
	7.  The Board hereby directs the Applicant to correct deficiency 7 by removing the cited combustibles under the stairwells.  However, the Applicant may utilize this area for storage, at the direction and to the satisfaction of the North Providence Fire Marshals Office if it is properly sheet-rocked off and detection is provided, within the timelines outlined in item 1 above.
	8.  It is the understanding of the Board that the Applicant is in the process of correcting deficiency 8.  Accordingly, the Board hereby grants the Applicant the time variance outlined in item 1 above in order to finish correcting this deficiency, at the direction and to the satisfaction of the North Providence Fire Marshals Office.

STATUS OF DECISION AND APPEAL RIGHTS
	This Decision represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicants timely and continued compliance with all of the directives of the Board. Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board.  (See: Board Rules and Regulations, section 6-2-17).
	Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  (See: Board Rules and Regulations, section 6-2-18.)  In the event of complete, timely and continued compliance with the full Decision of the Board, the above cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the Fire Code or a revision of the above-cited classification.  (See: Board Rules and Regulations, section 6-2-19).  

Such changes in use or occupancy of this facility, or failure to continually comply with the Boards Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in R.I.G.L. 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.  (See: Board Rules and Regulations, section 6-2-20).
	The Applicant may appeal the Boards Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth division of the District Court.  Commencement of such an action does not operate as an automatic stay of this Decision [R.I.G.L. 42-35-15(c)].
rhode island coat of arms A Rhode Island Government Web site