Fire Safety Code, Rhode Island

Decisions - Details

STATE OF RHODE ISLAND
(401) 889-5551 phone
(401) 889-5279 fax
711 TTY
FIRE SAFETY CODE - BOARD OF APPEAL AND REVIEW
560 Jefferson Boulevard
Suite 202
Warwick, RI 02886
DECISION
FILE NO.: 110054
LOCATION OF PREMISES: 751 West Shore Road
APPLICANT: Mr. James Casey 240 Warwick Neck Avenue Warwick, RI 02889
USE OR OCCUPANCY: Mercantile
DATE OF DECISION: 2011-06-09
The above-captioned case was scheduled for hearing before a subcommittee of the Board on March 22, 2011 at 1:00 P.M.  At that time, Chairman Newbrook and Commissioners Preiss, Walker and Dias were present.  The fire service was represented by Assistant Deputy State Fire Marshal Peter Marietti of the Warwick Fire Marshals Office.  A motion was made by Commissioner Dias and seconded by Commissioner Preiss to recommend that the Board grant the Applicant relief as outlined herein.  The motion was unanimous.

The above recommendations were thereupon consolidated with the subcommittee recommendations heard on March 17, 2011 and were presented to the Board on March 29, 2011 at 1:00 P.M.  At that time, Chairman Newbrook and Commissioners Preiss, Pearson, Jasparro, Dias and Walker were present.  A motion to approve the subcommittee recommendations was made by Commissioner Walker and seconded by Commissioner Pearson.  The motion was unanimous.  Accordingly, the subcommittee determination has the status of a full Board decision.

FINDINGS OF FACT
	The numbers of the Decision below correspond with those of a February 17, 2011 inspection report compiled by the Warwick Fire Marshals Office.  The above report was utilized by the Board, the Applicant and the Warwick Fire Marshals Office during the March 22, 2011 subcommittee hearing on this matter.  Accordingly, the Board hereby incorporates the February 17, 2011 inspection report as its initial findings of fact.  Any modification of the Boards findings, such as correction of a deficiency by the Applicant, shall be noted herein.
 
Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Applicant.  The term approved, as used herein, is understood to mean in accordance with the specific provisions related to the particular subject as are contained in this Code, or as approved in particular by the State Fire Marshal or his or her designee.

CONCLUSIONS AND VARIANCE REQUESTS 
	1.  The Board hereby grants the Applicant a time variance of thirty (30) days from the date of this decision in which to provide the Warwick Fire Marshals Office with a plan of action for the installation of a local fire alarm system.  The Board further grants the Applicant an additional 150 days in order to implement the above plan of action, at the direction and to the satisfaction of the Warwick Fire Marshals Office.  Finally, the Board notes that the Warwick Fire Marshals Office may extend either or both of the above timelines for good faith efforts being shown by the Applicant.
	2.  The Board hereby grants the Applicant the time variance outlined in item 1 above in order to provide this facility with any additional required emergency lighting and exit signage deemed necessary by the Warwick Fire Marshals Office.
	3.  The Board hereby directs the Applicant to correct deficiency 3 by providing this facility with approved fire extinguishers at the direction and to the satisfaction of the Warwick Fire Marshals Office.

STATUS OF DECISION AND APPEAL RIGHTS
	This Decision represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicants timely and continued compliance with all of the directives of the Board. Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board.  (See: Board Rules and Regulations, section 6-2-17).
	Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  (See: Board Rules and Regulations, section 6-2-18.)  In the event of complete, timely and continued compliance with the full Decision of the Board, the above cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the Fire Code or a revision of the above-cited classification.  (See: Board Rules and Regulations, section 6-2-19).  
Such changes in use or occupancy of this facility, or failure to continually comply with the Boards Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in R.I.G.L. 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.  (See: Board Rules and Regulations, section 6-2-20).
The Applicant may appeal the Boards decision within thirty (30) days of the mailing date of this decision by submitting a written appeal of the above subcommittee recommendations to the entire Fire Board for review, pursuant to Board Rule 6-2-9.  The Applicant shall thereupon be scheduled for hearing before the full Board of Appeal & Review.  Commencement of such an action does not operate as an automatic stay of this decision (RIGL 42-35-15(c)).
rhode island coat of arms A Rhode Island Government Web site