FIRE SAFETY CODE - BOARD OF APPEAL AND REVIEW
560 Jefferson Boulevard
Suite 202
Warwick, RI 02886
DECISION
FILE NO.: 010117
LOCATION OF PREMISES: 67 Gaulin Avenue
APPLICANT: Topik Enterprises, LLC P.O. Box 446 Harrisville, R.I. 02830
USE OR OCCUPANCY: Apartment
DATE OF DECISION: 2003-03-27
The above-captioned case was scheduled for hearing on June 5, 2001 at 1:30 P.M. At that time, Vice Chairman Richard and Commissioners Newbrook, O’Connell, Filippi and Burlingame were present.  The fire service was represented by Assistant Deputy State Fire Marshal Joseph Barroso of the Woonsocket Fire Marshal’s Office and Chief of Inspections William Howe of the State Fire Marshal’s Office.  An initial  motion was made by Commissioner Newbrook and seconded by Commissioner Filippi to grant the Applicant relief as outlined herein subject to agreement on a time frame.  The motion was unanimous. A follow-up motion, granting 150 days for the installation of the fire alarm system and an additional 210 days for the remaining items (except fire extinguishers) was then made by Commissioner Newbrook and seconded by Commissioner Filippi. However, pursuant to the request of the Applicant, this motion was modified to mandate compliance with the fire extinguishers within 15 days and complete compliance with the remaining directive of the decision within 120 days.  The modified motion was unanimous.  Accordingly, the fire extinguishers shall be installed on or before June 20, 2001 and the Applicant shall fully comply with the remainder of the decision on or before October 3, 2001.

FINDINGS OF FACT

The numbers of the Decision below correspond with those of an October 3, 2000 inspection report complied by the Woonsocket Fire Marshal’s Office.  The above report was utilized by the Board, the Applicant and the Woonsocket Fire Marshal’s Office during the June 5, 2001 hearing on this matter. Accordingly, the Board hereby incorporates the October 3, 2000 inspection report as its initial findings of fact.  Any modification of the Board’s findings, such as correction of a deficiency by the Applicant, shall be noted herein. 

Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Applicant.  The term “approved”, as used herein, is defined in section 23-28.1-4(3) of the Rhode Island General Laws.

CONCLUSIONS AND VARIANCE REQUESTS

1. The Board hereby grants a variance from the provisions of section 23-28.16-5 in order to allow the Applicant to maintain the existing construction and fire rating of the egress system walls of this facility.  In granting this variance, the Board directs the Applicant to provide the cited wainscoting with an approved Class-A finish at the direction and to the satisfaction of the Woonsocket Fire Marshal on or before October 3, 2001.

1(a). The Board hereby grants a variance from the provisions of section 23-28.16-5(f) in order to allow the Applicant to maintain the existing cited winding stairs within this facility.  In granting this variance, on the basis of structural hardship, it is the understanding of the Board that the Woonsocket Fire Marshal has no objection in light of the Applicant’s agreement to provide this facility with approved fire alarm system.

2.  The Board hereby grants a variance from the provisions of section 23-28.16-5 in order to allow the Applicant to maintain the existing cited egress system wall construction.  In granting this variance, on the basis of structural hardship, the Board directs the Applicant to provide the cited wainscoting with approved Class A finish installed at the direction and to the satisfaction of the Woonsocket Fire Marshal on or before October 3, 2001.

3. The Board hereby grants a variance from the provisions of section 23-28.16-6 in order to allow the Applicant to provide the existing apartment door jambs of this facility with approved solid core wood doors maintaining an approximate fire rating of twenty minutes.  The above doors shall be further equipped with spring loaded hinges and  installed at the direction and to the satisfaction of the Woonsocket Fire Marshal on or before October 3, 2001.  The Board further grants a variance from the above provisions in order to allow the Applicant to maintain the existing swing of the cited exterior doors.  This variance is granted on the basis of structural hardship in light of the Applicant’s agreement to provide this facility with approved fire alarm system.

4. The Board hereby grants a variance from the provisions of section 23-28.16-13 and NFPA standard 10, 1988 edition in order to allow the Applicant to provide each of the apartment units of this facility, and the basement, with approved fire extinguishers.  The above extinguishers shall be installed at the direction and to the satisfaction of the Woonsocket Fire Marshal by June 20, 2001.

5. As a condition of the variances granted herein, the Board hereby directs the Applicant to provide this facility with an approved local fire alarm system, installed in accordance with the provisions of section 23-28.25-4(a) at the direction and to the satisfaction of the Woonsocket Fire Marshal on or before October 3, 2001.

STATUS OF DECISION AND APPEAL RIGHTS

This Decision represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicant’s timely and continued compliance with all of the directives of the Board. Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board. (See: Board Rules and Regulations, section 6-2-17).

Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein. (See: Board Rules and Regulations, section 6-2-18)  In the event of complete, timely and continued compliance with the full Decision of the Board, the above cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the Fire Code or a revision of the above-cited classification. (See: Board Rules and Regulations, section 6-2-19).  

Such changes in use or occupancy of this facility, or failure to continually comply with the Board’s Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in R.I.G.L. 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy. (See: Board Rules and Regulations, section 6-2-20).
	
The Applicant may appeal the Board’s Decision, within thirty (30) days of 
the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth division of the District Court.  Commencement of such an action does not operate as an automatic stay of this Decision [R.I.G.L. 42-35-15(c)]