FIRE SAFETY CODE - BOARD OF APPEAL AND REVIEW
560 Jefferson Boulevard
Suite 202
Warwick, RI 02886
DECISION
FILE NO.: 200167
LOCATION OF PREMISES: 32-34 Catherine Street
APPLICANT: Pine Lodge Partnership c/o Henry R. Hole, Jr. 28 Weatherly Avenue Newport, R.I. 02840
USE OR OCCUPANCY: Apartment
DATE OF DECISION: 2003-04-07
The above-captioned case was scheduled for hearing on October 3, 2000 at 1:30 P.M.  At that time, Chairman Farrell and Commissioners Coutu, Wahlberg, Newbrook, O'Connell, Filippi, Burlingame and Pearson were present.  The fire service was represented by Assistant Deputy State Fire Marshal Michael Leber of the Newport Fire Marshal’s Office.  A motion was made by Commissioner Coutu and seconded by Commissioner Wahlberg to grant the Applicant relief as outlined herein.  The motion was unanimous.

FINDINGS OF FACT
	
The numbers of the Decision below correspond with those of an April 17, 2000 inspection report complied by the Newport Fire Marshal’s Office.  The above report was utilized by the Board, the Applicant and the Newport Fire Marshal’s Office during the  October 3, 2000 hearing on this matter.  Accordingly, the Board hereby incorporates the April 17, 2000 inspection report as its initial findings of fact.  Any modification of the Board’s findings, such as correction of a deficiency by the Applicant, shall be noted herein. 
	
Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Applicant.  The term “approved”, as used herein, is defined in section 23-28.1-4(3) of the Rhode Island General Laws.

CONCLUSIONS AND VARIANCE REQUESTS

1. The Board hereby grants a variance from the provisions of section 23-28.16-2 in order to allow the Applicant to maintain the existing egress system of this facility as modified herein.  In granting this variance, on the basis of structural hardship, it is the understanding of the Board that the Newport Fire Marshal's office has no objection.

2(a)&(b).The Board hereby grants a variance from the provisions of section 23-28.16-3 in order to allow the Applicant to maintain access to the cited stairway through the kitchens of this facility and to further allow the cited apartment unit to maintain a full step up to the rear door. 

3(a)(b)&(c).  The Board hereby grants a variance from the provisions of section 23-28.16-5 in order to allow the Applicant to maintain the existing rating, and winding nature, of the cited interior stairwells.  The Board directs the Applicant to correct deficiency 3(b) by providing this facility with handrails, at the direction and to the satisfaction of the Newport Fire Marshal, within 120 days of the date of this decision.

4(a)(b)&(c). The Board hereby grants a variance, from the provisions of section 23-28.16-6, in order to allow the Applicant to provide each of the apartment door jambs of this facility with an approved solid core wood doors maintaining an approximate fire rating of 20 minutes.  The above doors shall be installed with spring loaded hinges, at the direction and to the satisfaction of the Newport Fire Marshal, within under 120 days of the date of this decision.  Finally, the Board grants a variance from the above provisions to allow the cited doors to the exterior to maintain their existing swing.  In granting the above variances, it is the understanding of the Board that the Newport Fire Marshal's office has no objection.

5. It is the understanding of the Board that deficiency 5 is grandfathered and not being requested by the Newport Fire Marshal as a condition of the variances granted.

6. The Board hereby grants a variance from the provisions of section 23-28.16-13 and NFPA standard 10, 1988 edition in order to allow the Applicant to provide each of the apartment units of this facility with approved fire extinguishers, installed at the direction and to the satisfaction of the Newport Fire Marshal, within 15 days of the date of this decision.

7. As a condition of the variances granted herein, the Board hereby directs the Applicant to provide this facility with approved fire alarm system, the installed at the direction and to the satisfaction of the Newport fire Marshal or designee, in accordance with the provisions of section 23-28.25-4(a).

STATUS OF DECISION AND APPEAL RIGHTS
	
This Decision represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicant’s timely and continued compliance with all of the directives of the Board. Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board. (See: Board Rules and Regulations, section 6-2-17).
	
Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein. (See: Board Rules and Regulations, section 6-2-18)  In the event of complete, timely and continued compliance with the full Decision of the Board, the above cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the Fire Code or a revision of the above-cited classification. (See: Board Rules and Regulations, section 6-2-19).  

Such changes in use or occupancy of this facility, or failure to continually comply with the Board’s Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in R.I.G.L. 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy. (See: Board Rules and Regulations, section 6-2-20).
	
The Applicant may appeal the Board’s Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth division of the District Court.  Commencement of such an action does not operate as an automatic stay of this Decision [R.I.G.L. 42-35-15(c)].