Fire Safety Code, Rhode Island

Decisions - Details

STATE OF RHODE ISLAND
(401) 889-5551 phone
(401) 889-5279 fax
711 TTY
FIRE SAFETY CODE - BOARD OF APPEAL AND REVIEW
560 Jefferson Boulevard
Suite 202
Warwick, RI 02886
DECISION
FILE NO.: 070390
LOCATION OF PREMISES: 2154 West Main Road, Portsmouth
APPLICANT: Ms. Julia Forgue Newport Water Department 70 Halsey Street Newport, RI 02847
USE OR OCCUPANCY: Industrial
DATE OF DECISION: 2008-03-14
The above-captioned case was scheduled for hearing on October 30, 2007 at 1:00 P.M.  At that time, Chairman Coutu, Vice Chairman Newbrook and Commissioners Pearson, Filippi, Preiss, Blackburn, Jasparro, Jackson, Walker and Richard were present.  The fire service was represented by Assistant Deputy State Fire Marshal Phillip Simmons of the Portsmouth Fire Marshals Office.  A motion was made by Vice Chairman Newbrook and seconded by Commissioner Jackson to grant the Applicant relief as outlined herein.  The motion was unanimous.
FINDINGS OF FACT
	The numbers of the Decision below correspond with those of a June 6, 2007 inspection report compiled by the Portsmouth Fire Marshals Office.  The above report was utilized by the Board, the Applicant and the Portsmouth Fire Marshals Office during the October 30, 2007 hearing on this matter.  Accordingly, the Board hereby incorporates the June 6, 2007 inspection report as its initial findings of fact.  Any modification of the Boards findings, such as correction of a deficiency by the Applicant, shall be noted herein. 
	Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Applicant.  The term approved, as used herein, shall be understood to mean in accordance with the specific provisions related to the particular subject as are contained in the State Fire Code, or as approved in particular by the Authority Having Jurisdiction (the State Fire Marshal, his or her designated Deputy State Fire Marshals and/or Assistant Deputy State Fire Marshals).

CONCLUSIONS AND VARIANCE REQUESTS 
	1-2.  The Board hereby grants the Applicant a time variance of six (6) months from the date of this decision in order to develop a plan for approved suppression and approved fire alarm system covering this facility, in conjunction with the Portsmouth Fire Marshal's office.  In the event the Applicant needs additional time to develop these plans, the Applicant may return with the Portsmouth Fire Marshal to address that issue.
	3.  The Board hereby grants a variance from the provisions of section 7.11.1 and its referenced standards in order to allow the Applicant to maintain a single means of egress from the basement and the second floor of this facility.  In granting this variance, it is the understanding of the Board that the Portsmouth Fire Marshal's office has no objection with the Applicants agreement to sprinkler and alarm the high hazard areas.
	4.  The Board hereby grants the Applicant a time variance of six (6) months from the date of this decision in order to correct deficiency 4 by providing approved emergency lighting and exit signage in this facility at the direction and to the satisfaction of the Portsmouth Fire Marshal's office.
	5.  The Board hereby grants the Applicant a time variance of six (6) months from the date of this decision in order to correct deficiency 5 by properly segregating the boiler room of this facility at the direction and to the satisfaction of the Portsmouth Fire Marshal's office.
	6-8.  The Board hereby grants the Applicant a time variance of 120 days from the date of this decision in order to address the interior finish, the floor/ceiling penetrations and the self-closing doors that are required in Building 1 at the direction and to the satisfaction of the Portsmouth Fire Marshal's office.

STATUS OF DECISION AND APPEAL RIGHTS
	This Decision represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicants timely and continued compliance with all of the directives of the Board. Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board.  (See: Board Rules and Regulations, section 6-2-17).
	Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  (See: Board Rules and Regulations, section 6-2-18.)  In the event of complete, timely and continued compliance with the full Decision of the Board, the above cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the Fire Code or a revision of the above-cited classification.  (See: Board Rules and Regulations, section 6-2-19).  
Such changes in use or occupancy of this facility, or failure to continually comply with the Boards Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in R.I.G.L. 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.  (See: Board Rules and Regulations, section 6-2-20).
	The Applicant may appeal the Boards Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth division of the District Court.  Commencement of such an action does not operate as an automatic stay of this Decision [R.I.G.L. 42-35-15(c)].