DECISION
FILE NO.: 060148
LOCATION OF PREMISES: 2300 East Main Road, Portsmouth
APPLICANT: Chief Alan T. Adams 2300 East Main Road Portsmouth, RI 02871
USE OR OCCUPANCY: Business
DATE OF DECISION: 2006-09-19
The above-captioned case was scheduled for hearing on May 16, 2006 at 1:00 P.M.  At that time, Chairman Farrell, Vice Chairman Coutu and Commissioners Burlingame, Pearson, Newbrook and Richard were present.  The fire service was represented by Assistant Deputy State Fire Marshal Jeffrey Lynch of the Portsmouth Fire Marshals Office.  A motion was made by Commissioner Newbrook and seconded by Commissioner Richard to grant the Applicant relief as outlined herein.  The motion was unanimous.
FINDINGS OF FACT
	The numbers of the Decision below correspond with those of a December 29, 2004 inspection report compiled by the Portsmouth Fire Marshals Office.  The above report was utilized by the Board, the Applicant and the Portsmouth Fire Marshals Office during the May 16, 2006 hearing on this matter.  Accordingly, the Board hereby incorporates the December 29, 2004 inspection report as its initial findings of fact.  Any modification of the Boards findings, such as correction of a deficiency by the Applicant, shall be noted herein. 
	Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Applicant.  The term approved, as used herein, is understood to mean in accordance with the specific provisions related to the particular subject as are contained in this Code, or as approved in particular by the State Fire Marshal or his or her designee.

CONCLUSIONS AND VARIANCE REQUESTS 
	1.  The Board hereby grants a variance in order to allow the Applicant to maintain the existing cited metal door frames in concrete assemblies as an equivalent of the required one-hour rated assemblies.  
	2.  During the May 16, 2006 hearing on this matter, the Board was advised that there are two (2) full means of egress from the second floor.  The Board was further advised that the middle stairwell was not enclosed at the bottom.  However, the Board was advised that it was enclosed at the top.  Further, the Board was advised that this facility is protected with twenty-four hour fire fighter coverage and with a full coverage sprinkler system.  Accordingly, the Board hereby grants a variance from the provisions of section 39.3.1.1 in order to allow the middle stair of this facility to remain enclosed at the top but not at the bottom.  In granting this variance, the Board relies on the above fire protection features.

STATUS OF DECISION AND APPEAL RIGHTS
	This Decision represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicants timely and continued compliance with all of the directives of the Board. Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board.  (See: Board Rules and Regulations, section 6-2-17).
	Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  (See: Board Rules and Regulations, section 6-2-18.)  In the event of complete, timely and continued compliance with the full Decision of the Board, the above cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the Fire Code or a revision of the above-cited classification.  (See: Board Rules and Regulations, section 6-2-19).  
Such changes in use or occupancy of this facility, or failure to continually comply with the Boards Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in R.I.G.L. 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.  (See: Board Rules and Regulations, section 6-2-20).
	The Applicant may appeal the Boards Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth division of the District Court.  Commencement of such an action does not operate as an automatic stay of this Decision [R.I.G.L. 42-35-15(c)].