Fire Safety Code, Rhode Island

Decisions - Details

STATE OF RHODE ISLAND
(401) 889-5551 phone
(401) 889-5279 fax
711 TTY
FIRE SAFETY CODE - BOARD OF APPEAL AND REVIEW
560 Jefferson Boulevard
Suite 202
Warwick, RI 02886
DECISION
FILE NO.: 060835
LOCATION OF PREMISES: 175 Mathewson Street, Providence
APPLICANT: Grace Church c/o F. J.Newman & Son, Inc. 44 Newman Avenue Johnston, RI 02919
USE OR OCCUPANCY: Assembly
DATE OF DECISION: 2007-02-16
The above-captioned case was scheduled for hearing on October 24, 2006 at 1:00 P.M.  At that time, Chairman Coutu and Commissioners Richard, Blackburn, Preiss, Pearson, Filippi and OConnell were present.  The fire service was represented by Assistant Deputy State Fire Marshal Joseph Michalczyk of the Providence Fire Marshals Office.  A motion was made by Commissioner Blackburn and seconded by Commissioner Richard to grant the Applicant relief as outlined herein.  The motion was unanimous.
FINDINGS OF FACT
	The numbers of the Decision below correspond in sequence with those of a September 27, 2006 inspection report compiled by the Providence Fire Marshals Office.  The above report was utilized by the Board, the Applicant and the Providence Fire Marshals Office during the October 24, 2006 hearing on this matter.  Accordingly, the Board hereby incorporates the September 27, 2006 inspection report as its initial findings of fact.  Any modification of the Boards findings, such as correction of a deficiency by the Applicant, shall be noted herein. 
	Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Applicant.  The term approved, as used herein, is understood to mean in accordance with the specific provisions related to the particular subject as are contained in this Code, or as approved in particular by the State Fire Marshal or his or her designee.

CONCLUSIONS AND VARIANCE REQUESTS 
	1.  During the October 24, 2006 hearing on this matter, the Board was advised that the Applicant is planning to replace its current kitchen hood and duct system and that it is requesting a variance on the termination of the exhaust system approximately six (6) feet from the sidewalk.  The Board hereby grants a variance from the provisions of sections 8.1.1.1, 8.1.1.2 and referenced section 7.8.2.1 in order to allow the Applicant to maintain its upblast termination within the required ten (10) feet from the property line at a distance of approximately six (6) feet.  In order to address the limited distance allowed above, the Board directs the Applicant to provide separation in the form of fencing and/or vegetation from the updraft to the property line, at the direction and to the satisfaction of the Providence Fire Marshal's office.

STATUS OF DECISION AND APPEAL RIGHTS
	This Decision represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicants timely and continued compliance with all of the directives of the Board. Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board.  (See: Board Rules and Regulations, section 6-2-17).
	Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  (See: Board Rules and Regulations, section 6-2-18.)  In the event of complete, timely and continued compliance with the full Decision of the Board, the above cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the Fire Code or a revision of the above-cited classification.  (See: Board Rules and Regulations, section 6-2-19).  
Such changes in use or occupancy of this facility, or failure to continually comply with the Boards Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in R.I.G.L. 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.  (See: Board Rules and Regulations, section 6-2-20).
	The Applicant may appeal the Boards Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth division of the District Court.  Commencement of such an action does not operate as an automatic stay of this Decision [R.I.G.L. 42-35-15(c)].