Fire Safety Code, Rhode Island

Decisions - Details

STATE OF RHODE ISLAND
(401) 889-5551 phone
(401) 889-5279 fax
711 TTY
FIRE SAFETY CODE - BOARD OF APPEAL AND REVIEW
560 Jefferson Boulevard
Suite 202
Warwick, RI 02886
DECISION
FILE NO.: 010144
LOCATION OF PREMISES: 113 River Street
APPLICANT: Mr. William F. Egan 113 River Street Woonsocket, RI 02895
USE OR OCCUPANCY: Apartment
DATE OF DECISION: 2003-01-23
	The above captioned case was scheduled for hearing on December 4, 2001 at l:00 p.m.  At that time, Chairman Farrell and Commissioners Wahlberg, Newbrook, Filippi, Coutu, Richard and O’Connell were present.   The fire service was represented by Assistant Deputy State Fire Marshal Thomas Morris of the Woonsocket Fire Marshal’s Office.  A motion was made by Commissioner Newbrook and seconded by Commissioner Coutu to grant the Applicant relief as outlined herein.  The motion was unanimous.

FINDING OF FACT

The numbers of the Decision below correspond with those of an April 6, 2001 inspection report compiled by the Woonsocket Fire Marshal’s Office.  The above report was utilized by the Board, the Applicant and the Woonsocket Fire Marshal’s Office during the December 4, 2001 hearing on this matter.  Accordingly, the Board hereby incorporates the April 6, 2001 inspection report as its initial findings of fact.  Any modification of the Board’s findings such as correction of a deficiency shall be noted herein.
	
Any deficiency, understood by the Board, to have been corrected which is not so corrected shall be immediately corrected by the Applicant.  The term approved as used herein is defined in Section 23-28.l-4(3) of the Rhode Island General Laws.

CONCLUSIONS AND VARIANCE REQUESTS

1.	The Board hereby grants a variance from provisions of Section 23-28.l6-2 in order to allow the Applicant to maintain the egress system of this facility as modified herein.  In granting this variance on the basis of structural hardship, the Applicant shall be allowed to maintain his fire escapes provided there are no locks or locking devices on the bedroom doors leading to the fire escapes.  Finally, it is the understanding of the Board that the Woonsocket Fire Marshal’s Office has no objection in light of the Applicant’s agreement to provide this facility with an approved fire alarm system as outlined in item  #4 below.

2.	The Board hereby grants a variance from the provisions of Section 23-28.l6-5 & 6 in order to allow the Applicant to provide the cited apartment and basement door jambs of this facility with approved solid core wood doors maintaining an approximate fire rating of twenty (20) minutes.  The above doors shall be further installed with spring-loaded hinges and installed at the direction of the Woonsocket Fire Marshal, within one hundred and twenty (l20) days from the date of this Decision.  The Board further grants a variance in order to allow the Applicant to maintain the existing swing of the cited doors to the exterior from this facility.

3.	The Board hereby grants a variance from the provisions of Section 23-28.l6-l3 and NFPA Standard l0, l988 edition in order to allow the Applicant to provide individual approved fire extinguishers in each of the apartment units of this facility.  In granting this variance, the Board directs the Applicant to provide this facility with approved fire extinguishers within fifteen (l5) days from the date of this Decision.

4.	As a condition of the variances granted herein, the Board directs the Applicant to provide this facility with an approved fire alarm system, installed at the direction and to the satisfaction of the Woonsocket Fire Marshal or designee, in accordance with the provisions of Section 23-28.l6-l6 and 23-28.25-4(a), within one hundred and twenty (l20) days from the date of this Decision.

This Decision represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicant’s timely and continued compliance with all of the directives of the Board.  Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board.

Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  In the event of complete, timely and continued compliance with the full Decision of the Board, the above-cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the Fire Code or a revision of the above-cited classification.  Such changes in use or occupancy of this facility, or failure to continually comply with the Board’s Decision, shall void all variances granted under the above-cited use or occupancy.  If such changes creates a new use or occupancy as outlined in R.I.G.L. 23-28.l-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.

	The Applicant may appeal the Board’s Decision within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal within the Sixth Division of the District Court.  Commencement of such an action does not operate as an automatic stay of this Decision.  [RIGL 42-35-l5(c)]