Fire Safety Code, Rhode Island

Decisions - Details

STATE OF RHODE ISLAND
(401) 889-5551 phone
(401) 889-5279 fax
711 TTY
FIRE SAFETY CODE - BOARD OF APPEAL AND REVIEW
560 Jefferson Boulevard
Suite 202
Warwick, RI 02886
DECISION
FILE NO.: 040353
LOCATION OF PREMISES: 1509 Mendon Road, Cumberland, RI
APPLICANT: Mr. Michael Robertson 50 Mohawk Street Cumberland, RI 02864
USE OR OCCUPANCY: Day Care Centers
DATE OF DECISION: 2006-07-21
The above-captioned case was scheduled for hearing by a subcommittee of the Board on April 5, 2006 at 9:00 A.M.  At that time, Vice Chairman Coutu and Commissioners Blackburn, Filippi and Burlingame were present.  The fire service was represented by Deputy State Fire Marshal Christine Kent of the State Fire Marshals Office.  The subcommittee recommendations were reviewed by the full Board on April 18, 2006 and approved pursuant to a motion by Commissioner Newbrook and seconded by Commissioner Pearson.  Accordingly, the subcommittee recommendations now have the status of a full Board decision.

FINDINGS OF FACT
	The numbers of the Decision below correspond with those of a September 16, 2004 inspection report compiled by the State Fire Marshals Office. The above report was utilized by the Board, the Applicant and the State Fire Marshals Office during the April 5, 2006 subcommittee hearing on this matter.  Accordingly, the Board hereby incorporates the September 16, 2004 inspection report as its initial findings of fact.  Any modification of the Boards findings, such as correction of a deficiency by the Applicant, shall be noted herein. 
	Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Applicant.  The term approved, as used herein, is understood to mean in accordance with the specific provisions related to the particular subject as are contained in this Code, or as approved in particular by the State Fire Marshal or his or her designee.

CONCLUSIONS AND VARIANCE REQUESTS 
	1.  It is the understanding of the Board that the Applicant has corrected deficiency 1 by repairing the cited emergency lighting.
	2.  It is the understanding of the Board that the Applicant has corrected deficiency 2 by providing the fire alarm drill switch.
	3.  It is the understanding of the Board that the Applicant has corrected deficiency 3 by disabling or removing the cited locking mechanism on the art storage closet at the direction and to the satisfaction of the State Fire Marshal's office.
	4.  The Board hereby grants a variance from the provisions of section 7.2.2.2.1 in order to allow the Applicant to maintain the existing 28 width of the stairway leading to the basement of this facility.  This variance is granted on the basis of structural hardship in light of the limited use of the basement.
	5.  It is the understanding of the Board that the Applicant has corrected deficiency 5 by properly mounting the cited heat detector.
	6.  It is the understanding of the Board that the Applicant has corrected deficiency 6 by sealing off the cited pipe penetrations through the fire wall of this facility.
	7.  The Board hereby grants a variance from the provisions of section 17.2.2 in order to allow the Applicant to maintain the cited bulkhead as an emergency means of egress from the unoccupied basement of this facility.
	8.  The Board hereby grants the Applicant a time variance of sixty (60) days from the date of this decision in order to provide this facility with approved smoke and carbon monoxide detection installed at the direction and to the satisfaction of the State Fire Marshal's office.

STATUS OF DECISION AND APPEAL RIGHTS
	This Decision represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicants timely and continued compliance with all of the directives of the Board. Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board.  (See: Board Rules and Regulations, section 6-2-17).
	Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  (See: Board Rules and Regulations, section 6-2-18.)  In the event of complete, timely and continued compliance with the full Decision of the Board, the above cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the Fire Code or a revision of the above-cited classification. . (See: Board Rules and Regulations, section 6-2-19).  
Such changes in use or occupancy of this facility, or failure to continually comply with the Boards Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in R.I.G.L. 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy. . (See: Board Rules and Regulations, section 6-2-20).
	The Applicant may appeal the subcommittees recommendation to the full Board, within thirty (30) days of the mailing date of this Decision, by requesting such review in writing in accordance with the provisions of RIGL 23-28.3-5(b)4.  Commencement of such an appeal does not operate as an automatic stay of this Decision [R.I.G.L. 42-35-15(c)].