Fire Safety Code, Rhode Island

Decisions - Details

STATE OF RHODE ISLAND
(401) 889-5551 phone
(401) 889-5279 fax
711 TTY
FIRE SAFETY CODE - BOARD OF APPEAL AND REVIEW
560 Jefferson Boulevard
Suite 202
Warwick, RI 02886
DECISION
FILE NO.: 030283
LOCATION OF PREMISES: 80-92 Spring Street
APPLICANT: Stephan Grumback/Thomas & Carol Ward 3142 Mendon Road Cumberland, RI 02864
USE OR OCCUPANCY: Apartment
DATE OF DECISION: 2004-05-10
The above-captioned case was scheduled for hearing on August 26, 2003 at 1:00 P.M.  At that time, Chairman Farrell and Commissioners Wahlberg, Preiss, Newbrook, Evans, Burlingame and Coutu were present.  The fire service was represented by Assistant Deputy State Fire Marshal Joseph Barroso of the Woonsocket Fire Marshal’s Office.  A motion was made by Commissioner Burlingame and seconded by Commissioner Newbrook to grant the Applicant relief as outlined herein.  The motion was unanimous.

FINDINGS OF FACT
	
The numbers of the Decision below correspond with those of a August 13, 2003 inspection report compiled by the Woonsocket Fire Marshal’s Office.  The above report was utilized by the Board, the Applicant and the Woonsocket Fire Marshal’s Office during the August 26, 2003 hearing on this matter.  Accordingly, the Board hereby incorporates the August 13, 2003 inspection report as its initial findings of fact.  Any modification of the Board’s findings, such as correction of a deficiency by the Applicant, shall be noted herein.
	
Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Applicant.  The term “approved”, as used herein, is defined in section 23-28.1-4(3) of the Rhode Island General Laws.

CONCLUSIONS AND VARIANCE REQUESTS
	
1. The Board hereby grants a variance from the provisions of section 23-28.16-2 in order to allow the Applicant to maintain the existing egress system of this facility as modified herein.  In granting this variance, it is the understanding of the Board that the Woonsocket Fire Marshal has no objection in light of the Applicant agreement to provide this facility with an approved fire alarm system.  As a condition of this variance, the Board hereby directs the Applicant to provide class “A” finish on the pine boards within the egress system of this facility.
	
2. The Board hereby grants a variance from the provisions of section 23-28.16-3 in order to allow the Applicant to maintain the existing fire escape accesses route and to escape this building over a non rated roof area to a fire escape ladder.  In granting this variance, the Board directs the Applicant to provide this facility with approved metal grate across the cited combustible roof at the direction and to the satisfaction of the Woonsocket Fire Marshal within 120 days of the date of this decision.  The Board further directs the Applicant to remove all locks and locking devices on bathroom doors through which access to the fire escape system is achieved.
	
3. The Board hereby grants a variance from the provisions of section 23-28.16-5 in order to allow the Applicant to use the existing cited stairway within this facility.  This variance is contingent upon the Applicant compliance with the remaining directives of this decision and the Applicant providing this facility with an approved fire alarm system.
	
4. The Board hereby grants a variance from the provisions of section 23-28.16-5 in order to allow the Applicant to maintain the existing cited egress construction of this facility as outlined in item #3 above.
	
5. The Board hereby grants a variance from the provisions of section 23-28.16-5 in order to allow the Applicant to provide the existing egress door jambs of this facility with approved solid core wood doors maintaining an approximate fire rating of twenty (20) minutes. The above doors shall be further equipped with spring loaded hinges installed at the direction and to the satisfaction of the Woonsocket Fire Marshal, within 120 days of the date of this decision. 
	
6. It is the understanding of the Board that deficiency #6 is grandfathered and not being requested as a condition of the variance granted herein by the Woonsocket Fire Marshal’s Office.
	
7. As a condition of the variance granted herein, the Board hereby directs the Applicant to provide this facility with approved emergency lighting, installed at the direction and to the satisfaction of the Woonsocket Fire Marshal, within 120 days of the date of this decision.
	
8. The Board hereby directs the Applicant to correct deficiency #8 by providing this facility with approved fire extinguishers installed at the direction and to the satisfaction of the Woonsocket Fire Marshal, within fifteen(15) days of the date of this decision.	
	
9. As a condition of the variance granted herein, the Board hereby directs the Applicant to provide this facility with an approved fire alarm system, installed at the direction and to the satisfaction of the Woonsocket Fire Marshal, within 120 days of the date of this decision. 	
	
10. As a condition of the variance granted herein, the Board hereby directs the Applicant to provide the furnace within this facility with an approved remote shut off switch installed at the direction and to the satisfaction of the Woonsocket Fire Marshal, within 120 days of the date of this decision.

STATUS OF DECISION AND APPEAL RIGHTS
	
This Decision represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicant’s timely and continued compliance with all of the directives of the Board.  Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board. (See:  Board Rules and Regulations, section 6-2-17).
	
Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  (See: Board Rules and Regulations, section 6-2-18.)  In the event of complete, timely and continued compliance with the full Decision of the Board, the above cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the Fire Code or a revision of the above-cited classification.  (See: Board Rules and Regulations, section 6-2-19).  

Such changes in use or occupancy of this facility, or failure to continually comply with the Board’s Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in R.I.G.L. 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.  (See: Board Rules and Regulations, section 6-2-20).
	
The Applicant may appeal the Board’s Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth division of the District Court.  Commencement of such an action does not operate as an automatic stay of this Decision [R.I.G.L. 42-35-15(c)].