DECISION
FILE NO.: 060121A
LOCATION OF PREMISES: 525 Branch Avenue (St. Ann School), Providence, RI
APPLICANT: Diocese of Providence One Cathedral Square Providence, RI 02903
USE OR OCCUPANCY: Educational
DATE OF DECISION: 2008-05-14
The above-captioned case was scheduled for hearing on February 5, 2008 at 1:00 P.M.  At that time, Vice Chairman Newbrook and Commissioners Pearson, Jackson, Filippi, Walker, Preiss, Blackburn and Richard were present.  The fire service was represented by Assistant Deputy State Fire Marshal Vernon Dunlap of the Providence Fire Marshals Office.  A motion was made by Commissioner Walker and seconded by Commissioner Jackson to grant the Applicant relief as outlined herein.  The motion was unanimous.

FINDINGS OF FACT
	The numbers of the Decision below correspond with those of a December 10, 2007 inspection report compiled by the Providence Fire Marshals Office.  The above report was utilized by the Board, the Applicant and the Providence Fire Marshals Office during the February 5, 2008 hearing on this matter.  Accordingly, the Board hereby incorporates the December 10, 2007 inspection report as its initial findings of fact.  Any modification of the Boards findings, such as correction of a deficiency by the Applicant, shall be noted herein. 
	Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Applicant.  The term approved, as used herein, shall be understood to mean in accordance with the specific provisions related to the particular subject as are contained in the State Fire Code, or as approved in particular by the Authority Having Jurisdiction (the State Fire Marshal, his or her designated Deputy State Fire Marshals and/or Assistant Deputy State Fire Marshals).

CONCLUSIONS AND VARIANCE REQUESTS 
	1.  The Board hereby grants the Applicant a time variance of sixty (60) days from the date of this decision in order to test the doors to determine whether they were filled with asbestos or a less hazardous material prior to the installation of panic hardware on the doors.  In the event the Applicant determines that the doors were filled with asbestos and that providing them with updated panic hardware could pose a hazard, the Applicant is free to return to the Board to review an alternative plan of action.
	2-5.  The Board hereby directs the Applicant to address deficiencies 2, 3, 4 and 5 by performing as much work as possible and correcting these deficiencies within the above sixty day period.  Again, the Applicant may return with a modified plan of action depending upon the results of the testing outlined in item 1.

STATUS OF DECISION AND APPEAL RIGHTS
	This Decision represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicants timely and continued compliance with all of the directives of the Board. Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board.  (See: Board Rules and Regulations, section 6-2-17).
	Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  (See: Board Rules and Regulations, section 6-2-18.)  In the event of complete, timely and continued compliance with the full Decision of the Board, the above cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the Fire Code or a revision of the above-cited classification.  (See: Board Rules and Regulations, section 6-2-19).  
Such changes in use or occupancy of this facility, or failure to continually comply with the Boards Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in R.I.G.L. 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.  (See: Board Rules and Regulations, section 6-2-20).
	The Applicant may appeal the Boards Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth division of the District Court.  Commencement of such an action does not operate as an automatic stay of this Decision [R.I.G.L. 42-35-15(c)].