Fire Safety Code, Rhode Island

Decisions - Details

STATE OF RHODE ISLAND
(401) 889-5551 phone
(401) 889-5279 fax
711 TTY
FIRE SAFETY CODE - BOARD OF APPEAL AND REVIEW
560 Jefferson Boulevard
Suite 202
Warwick, RI 02886
DECISION
FILE NO.: 150119
LOCATION OF PREMISES: 192-198 Newport Avenue, East Providence, RI
APPLICANT: Jean DiMeo 5 Crystal Court Johnston, RI 02919
USE OR OCCUPANCY: Business
DATE OF DECISION: 2015-12-09
As indicated in the file, a hearing involving the above-captioned property was conducted on December 1, 2015 before the Fire Safety Code Board of Appeal and Review, pursuant to RI General Laws Section 23-28.3-5.
	In attendance at the hearing were the following:
COMMISSIONERS: Chairman Newbrook, Vice-Chairman Blackburn and Commissioners Booth, Filippi, Pearson, Sylvester, Thornton and Walker.
AUTHORITY HAVING JURISDICTION: Assistant Deputy State Fire Marshal Kenneth Botelho of the East Providence Fire Marshals Office.
APPLICANT: Richard DiMeo and Jesse Silva.
EXECUTIVE DIRECTOR: W. Keith Burlingame, Esq.

TRAVEL OF THE CASE

1.	This is an Application for Variance filed under R.I.G.L. Chapter 23-28.3, entitled the Fire Safety Code Board of Appeal and Review, and the Administrative Regulations promulgated thereunder.
2.	The Application was filed by Jean DiMeo (owner) of 5 Crystal Court, Johnston, RI dated November 19, 2015.
3.	The Application was received by the Board and File  150119 opened on November 20, 2015.
4.	A hearing on the Application was conducted on December 1, 2015 at 1:00 PM before the Fire Safety Code Board of Appeal and Review.
5.	After all evidence was presented at the hearing, a motion was made by Commissioner Sylvester and seconded by Commissioner Filippi to grant the Applicant relief as outlined herein.  The motion passed on a 7 to 1 vote with Vice-Chairman Blackburn voting in opposition.

RECORD OF THE CASE

The following documents are part of the administrative record for Appeal  150119 and are pertinent to the decision rendered:

1.	Variance Application  150119 dated November 19, 2015 and filed on November 20, 2015.
2.	East Providence Fire Marshals Office Inspection Report dated November 19, 2015.

EXHIBITS

The following documents were presented at the December 1, 2015 hearing as exhibits:

1.	Applicants photographs (3).

FINDINGS OF FACT

	Based on the testimony and evidence introduced at the hearing and a review of the administrative file, the Board makes the following Finding of Fact:

1.	The numbers of the Decision below correspond with those of the November 19, 2015 plan review letter report compiled by the East Providence Fire Marshals Office.  The above report was utilized by the Board, the Applicant and the East Providence Fire Marshals Office during the December 1, 2015 hearing on this matter.  Accordingly, the Board hereby incorporates the November 19, 2015 plan review report as its initial findings of fact.  Any modification of the Boards findings, such as correction of a deficiency by the Applicant, shall be noted herein.
2.	There is no objection by the East Providence Fire Marshals Office to the granting of the relief outlined herein.

CONCLUSIONS OF LAW AND
DETERMINATIONS ON VARIANCE REQUESTS

1.	The Board hereby grants the Applicant a variance from the provisions of RILSC section 39.3.1.1 by allowing the unprotected vertical opening created by the proposed interior stair.  In consideration of the relief granted herein, the Board directs the Applicant to provide domestically-supplied automatic sprinkler protection within the stair in accordance with RILSC section 9.7.1.2 and that a sprinkler waterflow alarm switch interfaced with the buildings fire alarm system be provided prior to occupancy of the second floor, at the direction and to the satisfaction of the East Providence Fire Marshal's Office.

Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Applicant.  The term approved, as used herein, is understood to mean in accordance with the specific provisions related to the particular subject as are contained in this Code, or as approved in particular by the Authority Having Jurisdiction (State Fire Marshal, his or her designated Deputy State Fire Marshals and/or Assistant Deputy State Fire Marshals).

STATUS OF DECISION AND APPEAL RIGHTS

1.	This Decision represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicants timely and continued compliance with all of the directives of the Board. Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board.  (See: Board Rules and Regulations, section 6-2-22).
2.	Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  (See: Board Rules and Regulations, section 6-2-23.)  In the event of complete, timely and continued compliance with the full Decision of the Board, the above cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the Fire Code or a revision of the above-cited classification.  (See: Board Rules and Regulations, section 6-2-24).
3.	Such changes in use or occupancy of this facility, or failure to continually comply with the Boards Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in R.I.G.L. 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.  (See:  Board Rules and Regulations, section 6-2-25).
4.	The Applicant may appeal the Boards Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth Division of the District Court.  (See: Board Rules and Regulations, section 6-2-18).  Commencement of such an action does not operate as an automatic stay of this Decision [R.I.G.L. 42-35-15(c)].