FIRE SAFETY CODE - BOARD OF APPEAL AND REVIEW
560 Jefferson Boulevard
Suite 202
Warwick, RI 02886
DECISION
FILE NO.: 020133
LOCATION OF PREMISES: 196 Fuller Avenue, Central Falls, RI
APPLICANT: Louis Allen 54 South Street Cranston, RI 02920
USE OR OCCUPANCY: Apartment
DATE OF DECISION: 2002-09-11
The above captioned case was scheduled for hearing on July 9, 2002 at 1:00 P.M.  At that time, Chairman Farrell and Commissioners Richard, Pearson, Filippi, Preiss, Wahlberg, and OConnell were present.  Commissioner Coutu recused himself from this hearing.  The fire service was represented by Assistant Deputy State Fire Marshal John Garvey of the Central Falls Fire Marshals Office.  A motion was made by Commissioner Pearson and seconded by Commissioner Preiss, to grant the Applicant relief as outlined herein.  The motion was unanimous.

FINDINGS OF FACT
	The numbers of the Decision below correspond with those of a May 23, 2002 inspection report compiled by the Central Falls Fire Marshals Office.  The above report was utilized by the Board, the Applicant and the Central Falls Fire Marshals Office during the July 9, 2002 hearing on this matter.  Accordingly, the Board hereby incorporates the May 23, 2002 inspection report as its initial findings of fact.  Any modification of the Boards findings such as correction of a deficiency by the Applicant shall be noted herein.
	Any deficiency, understood by the Board, to have been corrected which is not so corrected shall be immediately corrected by the Applicant.  The term approved as used herein is defined in Section 23-28.1-4(3) of the Rhode Island General Laws.
	
CONCLUSIONS AND VARIANCE REQUESTS 
1.	The Board hereby directs the Applicant to correct deficiency 1 by providing this facility with an approved remote boiler shutoff switch at the top of the cellar stairs.  The above switch shall be installed at the direction and to the satisfaction of the Central Falls Fire Marshals Office, within one hundred and twenty (120) days from the date of this Decision.
2.	The Board hereby grants a variance from the provisions of Section 23-28.16-2 in order to allow the Applicant to maintain the existing egress system of this facility as modified herein.  This variance is granted pursuant to the Applicants agreement to provide this facility with an approved fire alarm system and other fire safety upgrades as modified herein.
3.	The Board hereby grants a variance from the provisions of Section 23-28.16-5 in order to allow the Applicant to maintain the existing construction of the walls and ceilings within this facility.  The Board further grants a variance from the above provisions in order to allow the Applicant to provide the existing egress system door jambs of this facility with approved solid core wood doors maintaining an approximate fire rating of twenty (20) minutes.  The above doors shall be further equipped with spring-loaded hinges and installed at the direction and to the satisfaction of the Central Falls Fire Marshals Office, within one hundred and twenty (120) days from the date of this Decision.
4.	As outlined in item 3 above, the Board hereby grants a variance from the provisions of Section 23-28.16-6 in order to allow the Applicant to provide the cited doors with approved spring-loaded hinges, installed at the direction and to the satisfaction of the Central Falls Fire Marshals Office, within one hundred and twenty (120) days from the date of this Decision.
5.	As outlined in item 3 above, the Board hereby grants a variance from the provisions of Section 23-28.16-6 in order to allow the Applicant to provide each of the apartment door jambs of this facility with an approved solid core door maintaining an approximate fire rating of twenty (20) minutes.
6.	The Board hereby directs the Applicant to provide this facility with an approved Class A paper or metal externally illuminated exit sign, installed at the direction and to the satisfaction of the Central Falls Fire Marshals Office within one hundred and twenty (120) days from the date of this Decision.
7.	As a condition of the variances granted herein, the Board directs the Applicant to provide this facility with approved emergency lighting, installed at the direction and to the satisfaction of the Central Falls Fire Marshal, within one hundred and twenty (120) days from the date of this Decision.
8.	The Board hereby grants a variance from the provisions of Section 23-28.16-13 and NFPA Standard 10, 1988 edition, in order to allow the Applicant to provide each of the apartment units with approved fire extinguishing equipment, installed at the direction and to the satisfaction of the Central Falls Fire Marshals Office, within fifteen (15) days from the date of this Decision.
9.	As a condition of the variances granted herein, the Board directs the Applicant to provide this facility with an approved local fire alarm system, installed at the direction and to the satisfaction of the Central Falls Fire Marshals Office, in accordance with the provisions of Section 23-28.16-6 and the local fire alarm provisions of the newly adopted state fire alarm code.

	This Decision represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicants timely and continued compliance with all of the directives of the Board. Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board.  
	Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.   In the event of complete, timely and continued compliance with the full Decision of the Board, the above cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the Fire Code or a revision of the above-cited classification.  Such changes in use or occupancy of this facility, or failure to continually comply with the Boards Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in R.I.G.L. 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.  
	The Applicant may appeal the Boards Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth division of the District Court.  Commencement of such an action does not operate as an automatic stay of this Decision [R.I.G.L. 42-35-15(c)].