Fire Safety Code, Rhode Island

Decisions - Details

STATE OF RHODE ISLAND
(401) 889-5551 phone
(401) 889-5279 fax
711 TTY
FIRE SAFETY CODE - BOARD OF APPEAL AND REVIEW
560 Jefferson Boulevard
Suite 202
Warwick, RI 02886
DECISION
FILE NO.: 020246
LOCATION OF PREMISES: 21 Peirce Street
APPLICANT: Mr. Carlo Russo 119 ½ Central Pike Foster, RI 02825
USE OR OCCUPANCY: Apartment
DATE OF DECISION: 2004-03-02
The above-captioned case was scheduled for hearing on October 21, 2003 at 1:00 P.M.  At that time, Chairman Farrell and Commissioners Wahlberg, Pearson, Evans, Burlingame, Coutu, Filippi and O’Connell were present.  The fire service was represented by Assistant Deputy State Fire Marshal Susan Hawksley of the East Greenwich Fire Marshal’s Office.  A motion was made by Commissioner Burlingame and seconded by Commissioner Coutu to grant the Applicant relief as outlined herein.  The motion was unanimous.

FINDINGS OF FACT
	
The numbers of the Decision below correspond with those of a July 15, 2002 inspection  report compiled by the East Greenwich Fire Marshal’s Office.  The above report was utilized by the Board, the Applicant and the East Greenwich Fire Marshal’s Office during the October 21, 2003 hearing on this matter.  Accordingly, the Board hereby incorporates the July 15, 2002 inspection report as its initial findings of fact.  Any modification of the Board’s findings, such as correction of a deficiency by the Applicant, shall be noted herein. 
	
Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Applicant.  The term “approved”, as used herein, is defined in section 23-28.1-4(3) of the Rhode Island General Laws.

CONCLUSIONS AND VARIANCE REQUESTS
	
1.  The Board hereby grants a variance from the provisions of section 23-28.16-2 in order to allow the Applicant to maintain the existing egress system of this facility as modified herein.  In granting this variance, the Board notes that the Applicant shall provide this facility with an approved fire alarm system as outlined in item #6 below, and accordingly the East Greenwich Fire Marshal’s office has no objection.
	
2.  The Board hereby grants a variance from the provisions of section 23-28.16-3 in order to allow the Applicant to maintain the existing construction and rating of the cited egress system walls of this facility.  In granting this variance, the Board notes that there is no wainscoting on the walls, and that they are in good condition, and that the East Greenwich Fire Marshal’s office has no objection to this relief.
	
3.  The Board hereby grants a variance from the provisions of section 23-28.16-5 in order to allow the Applicant to maintain the existing enclosure and rating of the stairways within this facility.  In granting this variance, it is the understanding of the Board that the East Greenwich Fire Marshal’s office has no objection in light of the Applicant’s agreement to provide this facility with an approved fire alarm system.
	
4.  The Board hereby grants a variance from the provisions of section 23-28.16-5(f) in order to allow the Applicant to maintain the existing winding stairs within the stairway system of this facility.  In granting this variance, it is the understanding of the Board that the East Greenwich Fire Marshal’s office has no objection in light of the Applicant’s agreement to provide this facility with an approved fire alarm system.
	
5.  The Board hereby grants a variance from the provisions of section 23-28.16-6 in order to allow the Applicant to maintain the existing swing of the cited doors on the basis of structural hardship.  The Board further grants a variance from the above section in order to allow the Applicant to provide the egress system door jambs of this facility with approved solid core doors maintaining an approximate fire rating of twenty (20) minutes.  The above doors shall be further equipped with spring loaded hinges installed at the direction and to the satisfaction of the East Greenwich Fire Marshal’s office within 120 days of the date of this decision.
	
6.  As a condition of the variances granted herein, the Board hereby directs the Applicant to provide this facility with an approved fire alarm system, installed at the direction and to the satisfaction of  the East Greenwich Fire Marshal’s office, within 120 days of the date of this decision.
	
7.  The Board hereby grants a variance in order to allow the Applicant to provide each of the apartment units of this facility with approved fire extinguishers, installed at the direction and to the satisfaction of the East Greenwich Fire Marshal’s office.  It is the understanding of the Board that the extinguishers are currently in place.
	
8.  The Board hereby directs the Applicant to provide the furnace of this facility with an approved domestically supplied sprinkler head, and to further provide it with an approved remote shut off switch and a twenty (20) minute door leading into the furnace room.  The above corrections shall be at the direction and to the satisfaction of the East Greenwich Fire Marshal’s office within 120 days of the date of this decision.

STATUS OF DECISION AND APPEAL RIGHTS
	
This Decision represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicant’s timely and continued compliance with all of the directives of the Board.  Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board. (See:  Board Rules and Regulations, section 6-2-17).
	
Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  (See: Board Rules and Regulations, section 6-2-18.)  In the event of complete, timely and continued compliance with the full Decision of the Board, the above cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the Fire Code or a revision of the above-cited classification.  (See: Board Rules and Regulations, section 6-2-19).  

Such changes in use or occupancy of this facility, or failure to continually comply with the Board’s Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in R.I.G.L. 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.  (See: Board Rules and Regulations, section 6-2-20).
	
The Applicant may appeal the Board’s Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth division of the District Court.  Commencement of such an action does not operate as an automatic stay of this Decision [R.I.G.L. 42-35-15(c)].

Decision mailed on 1-21-04.