DECISION
FILE NO.: 2023006
LOCATION OF PREMISES: 361 Privilege Street, Woonsocket, RI
APPLICANT: Steven Mineau 600 Cass Avenue Woonsocket, RI 02895
USE OR OCCUPANCY: Apartment
DATE OF DECISION: 2023-04-06
As documented in the file, a hearing involving the above-captioned property was conducted on Tuesday, March 21, 2023 before the Fire Safety Code Board of Appeal and Review [hereinafter the Board], pursuant to Rhode Island General Laws [RIGL] sections 23-28.3-5, 42-35-9 and 42-46-3.

	Participating at the hearing were the following:
COMMISSIONERS: Chairman Newbrook and Commissioners Thornton, ODonnell, Muto and Spaziani.
AUTHORITY HAVING JURISDICTION: Assistant Deputy State Fire Marshal Scott Hampson of the Woonsocket Fire Marshals Office.
APPLICANT: Steve Mineau.
EXECUTIVE DIRECTOR: W. Keith Burlingame, Esq.

TRAVEL OF THE CASE

1.	This is an Application for Variance filed under RIGL chapter 23-28.3, entitled Fire Safety Code Board of Appeal and Review, and the Administrative Regulations promulgated thereunder.
2.	The Application was filed by Steve Mineau (owner) of 600 Cass Avenue, Woonsocket, RI dated [undated].
3.	The Application was received by the Board and File  2023006 was opened on January 12, 2023.
4.	A hearing on the Application was conducted on March 21, 2023 at 1:00 PM before the Fire Safety Code Board of Appeal and Review.
5.	After consideration of the application, the testimony of the witnesses and of the entire record presented to the Board, and after carefully reviewing such information, a motion was made by Commissioner Thornton and seconded by Commissioner Spaziani to grant the Applicant the relief as outlined herein.  The motion passed on a 5 to 0 vote.

RECORD OF THE CASE

The following documents are part of the administrative record for Appeal  2023006 and are pertinent to the decision rendered:

1.	Variance Application  2023006 dated [undated] and filed on January 12, 2023.
a.	Letter of Authorization for Steve Mineau from John Boucher dated January 6, 2023.
2.	Woonsocket Fire Marshals Office Inspection Report dated November 10, 2022.

EXHIBITS

The following documents were presented at the March 21, 2023 hearing as exhibits:

1.	None.

FINDINGS OF FACT

	Based on the testimony and evidence introduced at the hearing and a review of the administrative file, the Board makes the following Findings of Fact:

1.	The numbers of the determinations below correspond with those of the November 10, 2022 inspection report compiled by the Woonsocket Fire Marshals Office.  The above report was utilized by the Board, the Applicant and the Woonsocket Fire Marshals Office during the March 21, 2023 hearing on this matter.  Accordingly, the Board hereby incorporates the November 10, 2022 inspection report as its initial findings of fact.  Any modification of the Boards findings, such as correction of a deficiency by the Applicant, shall be noted herein.
2.	The building is an existing 2/3-story above grade building with a basement level, classified as an apartment (6 unit) occupancy, consisting of approximately five thousand seven hundred twelve (5,712) square feet (living area) and originally built in 1963.
3.	The building is of Type V (000) construction, does not have a compliant fire alarm system and is not provided with an approved automatic sprinkler system.
4.	Battery operated smoke alarms and carbon monoxide (CO) alarms are provided in the buildings dwelling units.
5.	There is no objection by the Woonsocket Fire Marshals Office to the granting of the relief outlined herein.

CONCLUSIONS OF LAW AND
DETERMINATIONS ON VARIANCE REQUESTS

References to NFPA shall mean the National Fire Protection Association; references to the Rhode Island Fire Code [RIFC] shall mean NFPA 1, (2018 edition) as incorporated by reference and amended by 450-RICR-00-00-7; and, references to the Rhode Island Life Safety Code [RILSC] shall mean NFPA 101, (2018 edition) as incorporated by reference and amended by 450-RICR-00-00-8.

1.	FIRE ALARM SYSTEM: The Board hereby grants the Applicant a time variance of thirty (30) days from the date of the decision to comply with the provisions of RILSC section 31.1.1.1 (Option 2) by installing an approved fire alarm system in accordance with section 9.6 throughout the facility, at the direction and to the satisfaction of the Woonsocket Fire Marshals Office.
2.	This deficiency/violation will be corrected with the completion of item  1, above.
3.	This deficiency/violation has been corrected.
4.	This deficiency/violation has been corrected.
5.	This deficiency/violation has been corrected.
6.	This deficiency/violation has been corrected.
7.	This deficiency/violation has been corrected.
8.	EGRESS: The Board hereby grants the Applicant a time variance of ninety (90) days from the date of the decision to comply with the provisions of RILSC section 31.1.1.3 by repairing or replacing the window in the second floor  left unit that accesses the fire escape, at the direction and to the satisfaction of the Woonsocket Fire Marshals Office.
9.	This deficiency/violation has been corrected.
10.	This deficiency/violation has been corrected.
11.	This deficiency/violation has been corrected.
12.	This deficiency/violation has been corrected.
13.	EGRESS: The Board hereby grants the Applicant a time variance of ninety (90) days from the date of the decision to comply with the provisions of RILSC section 31.2.1.1, 24.2.2.1 and 24.2.2.3 by providing approved secondary means of escape for the basement units (including interior steps as necessary), at the direction and to the satisfaction of the Woonsocket Fire Marshals Office.  In consideration of the relief granted herein, the Board directs the Applicant to implement provisions whereby only able-bodied tenants are leased the basement units based upon the limitations in accessibility.
14.	This deficiency/violation will be corrected with the completion of item  13, above.

Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Applicant.  The term approved, as used herein, is understood to mean in accordance with the specific provisions related to the particular subject as are contained in this Code, or as approved in particular by the Authority Having Jurisdiction (State Fire Marshal, his or her designated Deputy State Fire Marshals and/or Assistant Deputy State Fire Marshals).

Finally, the Board hereby authorizes the Woonsocket Fire Marshals Office, upon receiving a written request, to extend the above timeline(s) for good faith compliance efforts being demonstrated by the Applicant by one (1) or more extensions of time of not more than thirty (30) days each, for a period not to exceed ninety (90) days in accordance with the provisions of 450-RICR-00-00-1.7.2(X).

STATUS OF DECISION AND APPEAL RIGHTS

1.	This Decision constitutes a final order of the Fire Safety Code Board of Appeal and Review as set forth in RIGL section 42-35-12 and represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicants timely and continued compliance with all of the directives of the Board.  Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board.  [See: Fire Safety Code [FSC] section 450-RICR-00-00-1.7.2(W)].
2.	Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  [See: FSC section 450-RICR-00-00-1.7.2(Y)].  In the event of complete, timely and continued compliance with the full Decision of the Board, the above cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the FSC or a revision of the above-cited classification.  [See: FSC section 450-RICR-00-00-1.7.2(Z)].
3.	Such changes in use or occupancy of this facility, or failure to continually comply with the Boards Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in RIGL section 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.  [See:  FSC section 450-RICR-00-00-1.7.2(AA)].
4.	In accordance with RIGL section 23-28.3-5(e), any person who violates a final order of the Board may be subject to prosecution in the District Court with possible imprisonment for a term not exceeding one (1) year, or fined not more than one thousand dollars (1000) for each offense.
5.	In accordance with RIGL section 42-35-12, the Applicant may appeal the Boards Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth Division of the District Court.  [See: RIGL section 23-28.3-6 and FSC section 450-RICR-00-00-1.7.2(S)].  Commencement of such an action does not operate as an automatic stay of this Decision [See: RIGL section 42-35-15(c)].