Fire Safety Code, Rhode Island

Decisions - Details

STATE OF RHODE ISLAND
(401) 889-5551 phone
(401) 889-5279 fax
711 TTY
FIRE SAFETY CODE - BOARD OF APPEAL AND REVIEW
560 Jefferson Boulevard
Suite 202
Warwick, RI 02886
DECISION
FILE NO.: 2023096
LOCATION OF PREMISES: 54 Barker Avenue, Warren, RI
APPLICANT: Benjamin Lescault 54 Barker Avenue Warren, RI 02885
USE OR OCCUPANCY: Health Care
DATE OF DECISION: 2023-08-10
As documented in the file, a hearing involving the above-captioned property was conducted on Tuesday, August 1, 2023 before the Fire Safety Code Board of Appeal and Review [hereinafter the Board], pursuant to Rhode Island General Laws [RIGL] sections 23-28.3-5, 42-35-9 and 42-46-3.

	Participating at the hearing were the following:
COMMISSIONERS: Chairman Newbrook and Commissioners Pearson, Sylvester, Thornton, Davison and ODonnell.
AUTHORITY HAVING JURISDICTION [AHJ]: Deputy State Fire Marshal Traci Choiniere of the State Fire Marshals Office.
APPLICANT: Benjamin Lescault.
EXECUTIVE DIRECTOR: W. Keith Burlingame, Esq.

TRAVEL OF THE CASE

1.	This is an Application for Variance filed under RIGL chapter 23-28.3, entitled Fire Safety Code Board of Appeal and Review, and the Administrative Regulations promulgated thereunder.
2.	The Application was filed by Benjamin Lescault (authorized representative) of 54 Barker Avenue, Warren, RI dated May 31, 2023.
3.	The Application was received by the Board and File  2023096 was opened on June 19, 2023.
4.	A hearing on the Application was conducted on August 1, 2023 at 1:00 PM before the Fire Safety Code Board of Appeal and Review.
5.	After consideration of the application, the testimony of the witnesses and of the entire record presented to the Board, and after carefully reviewing such information, a motion was made by Commissioner Thornton and seconded by Commissioner Davison to grant the Applicant the relief as outlined herein.  The motion passed on a 6 to 0 vote.

RECORD OF THE CASE

The following documents are part of the administrative record for Appeal  2023096 and are pertinent to the decision rendered:

1.	Variance Application  2023096 dated May 31, 2023 and filed on June 19, 2023.
a.	Letter of authorization for Benjamin Lescault from Mark Lescault dated May 31, 2023.
2.	State Fire Marshals Office Inspection Report dated May 25, 2023.
3.	Reschedule Notice dated July 24, 2023.

EXHIBITS

The following documents were presented at the August 1, 2023 hearing as exhibits:

1.	None.

FINDINGS OF FACT

	Based on the testimony and evidence introduced at the hearing and a review of the administrative file, the Board makes the following Findings of Fact:

1.	The numbers of the determinations below correspond with those of the May 25, 2023 inspection report compiled by the State Fire Marshals Office.  The above report was utilized by the Board, the Applicant and the State Fire Marshals Office during the August 1, 2023 hearing on this matter.  Accordingly, the Board hereby incorporates the May 25, 2023 inspection report as its initial findings of fact.  Any modification of the Boards findings relating to this report, such as correction of a deficiency by the Applicant, shall be noted herein.
2.	The building is an existing 1-story above grade building with a basement level, classified as a health care occupancy, consisting of approximately thirty-three thousand two hundred eight (33,208) square feet (net area) and originally built in 1966.
3.	The building is of Type V (111) construction, has a compliant fire alarm system with emergency forces notification and is provided with an approved automatic sprinkler system.
4.	The facility has been licensed by RIDOH for forty-four (44) residents.
5.	There is no objection by the State Fire Marshals Office to the granting of the relief outlined herein.

CONCLUSIONS OF LAW AND
DETERMINATIONS ON VARIANCE REQUESTS

References to NFPA shall mean the National Fire Protection Association; references to the Rhode Island Fire Code [RIFC] shall mean NFPA 1, (2018 edition) as incorporated by reference and amended by 450-RICR-00-00-7; and, references to the Rhode Island Life Safety Code [RILSC] shall mean NFPA 101, (2018 edition) as incorporated by reference and amended by 450-RICR-00-00-8.

1.	FIRE ALARM SYSTEM: The Board hereby grants the Applicant a time variance of thirty (30) days from the date of the decision to comply with the provisions of RILSC section 9.6 and NFPA 72 section 10.18.3 by developing and submitting a plan of action for the installation of an approved fire alarm system annunciator for the facility.  The Board further grants the Applicant an additional one hundred fifty (150) days in order to implement the above plan of action, at the direction and to the satisfaction of the State Fire Marshals Office.
2.	EGRESS: The Board hereby grants the Applicant a variance from the provisions of RILSC sections 19.2.1 and 7.1.5 by allowing the existing pipes in the basement level to remain in use without modification at sixty-nine (69) inches AFF based upon a structural hardship.  In consideration of the relief granted herein, the Board directs the Applicant to limit this area to employees only and to provide hazard markings, at the direction and to the satisfaction of the State Fire Marshal's Office.
3.	EXTINGUISHMENT: The Board hereby grants the Applicant a time variance of one (1) year from the date of the decision to comply with the provisions of RILSC section 19.3.5 and NFPA 25 section 5.3.1.1.1 by providing this facility with an approved supervised automatic sprinkler system in accordance with section 9.7, at the direction and to the satisfaction of the State Fire Marshal's Office.
4.	EXTINGUISHMENT: The Board hereby grants the Applicant a time variance of one (1) year from the date of the decision to comply with the provisions of RILSC section 19.3.5 and NFPA 13 section 8.3.3.2 by providing this facility with an approved supervised automatic sprinkler system in accordance with section 9.7, at the direction and to the satisfaction of the State Fire Marshal's Office.
5.	EGRESS: The Board hereby grants the Applicant the time variance set forth in item  1 above to comply with the provisions of RILSC sections 19.2.1 and 7.4.1 by providing this facility with an approved second exit from the basement by replacing the existing exterior bulkhead door with a side-swinging door, at the direction and to the satisfaction of the State Fire Marshals Office.

Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Applicant.  The term approved, as used herein, is understood to mean in accordance with the specific provisions related to the particular subject as are contained in this Code, or as approved in particular by the Authority Having Jurisdiction (State Fire Marshal, his or her designated Deputy State Fire Marshals and/or Assistant Deputy State Fire Marshals).

Finally, as it relates to violation  1 and 5 only, the Board hereby authorizes the State Fire Marshals Office, upon receiving a written request, to extend the above timeline(s) for good faith compliance efforts being demonstrated by the Applicant by one (1) or more extensions of time of not more than thirty (30) days each, for a period not to exceed ninety (90) days in accordance with the provisions of 450-RICR-00-00-1.7.2(X).

STATUS OF DECISION AND APPEAL RIGHTS

1.	This Decision constitutes a final order of the Fire Safety Code Board of Appeal and Review as set forth in RIGL section 42-35-12 and represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicants timely and continued compliance with all of the directives of the Board.  Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board.  [See: Fire Safety Code [FSC] section 450-RICR-00-00-1.7.2(W)].
2.	Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  [See: FSC section 450-RICR-00-00-1.7.2(Y)].  In the event of complete, timely and continued compliance with the full Decision of the Board, the above-cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the FSC or a revision of the above-cited classification.  [See: FSC section 450-RICR-00-00-1.7.2(Z)].
3.	Such changes in use or occupancy of this facility, or failure to continually comply with the Boards Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in RIGL section 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.  [See:  FSC section 450-RICR-00-00-1.7.2(AA)].
4.	In accordance with RIGL section 23-28.3-5(e), any person who violates a final order of the Board may be subject to prosecution in the District Court with possible imprisonment for a term not exceeding one (1) year, or fined not more than one thousand dollars (1000) for each offense.
5.	In accordance with RIGL section 42-35-12, the Applicant may appeal the Boards Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth Division of the District Court.  [See: RIGL section 23-28.3-6 and FSC section 450-RICR-00-00-1.7.2(S)].  Commencement of such an action does not operate as an automatic stay of this Decision [See: RIGL section 42-35-15(c)].
rhode island coat of arms A Rhode Island Government Web site