Fire Safety Code, Rhode Island

Decisions - Details

STATE OF RHODE ISLAND
(401) 889-5551 phone
(401) 889-5279 fax
711 TTY
FIRE SAFETY CODE - BOARD OF APPEAL AND REVIEW
560 Jefferson Boulevard
Suite 202
Warwick, RI 02886
DECISION
FILE NO.: 2023139
LOCATION OF PREMISES: 1675 Diamond Hill Road, Woonsocket, RI
APPLICANT: James Williams 141 Main Street Woonsocket, RI 02895
USE OR OCCUPANCY: Day Care Centers
DATE OF DECISION: 2023-09-27
As documented in the file, a hearing involving the above-captioned property was conducted on Tuesday, September 19, 2023 before the Fire Safety Code Board of Appeal and Review [hereinafter the Board], pursuant to Rhode Island General Laws [RIGL] sections 23-28.3-5, 42-35-9 and 42-46-3. 

 
In attendance at the hearing were the following: 

COMMISSIONERS: Chairman Newbrook, Vice-Chairman Blackburn and Commissioners Pearson, Sylvester, Booth, Thornton, Davison, ODonnell, Muto and Spaziani. 

AUTHORITY HAVING JURISDICTION [AHJ]:  State Fire Marshal Robert Couture of the State Fire Marshals Office. 

APPLICANT: James Williams and Robert Purcell. 

EXECUTIVE DIRECTOR: W. Keith Burlingame, Esq. 


TRAVEL OF THE CASE 

 
This is an Application for Variance filed under RIGL chapter 23-28.3, entitled Fire Safety Code Board of Appeal and Review, and the Administrative Regulations promulgated thereunder. 

The Application was filed by James Williams (&8203;owner&8203;) of 141 Main Street, Woonsocket, RI dated &8203;September 6, 2023&8203;. 

The Application was received by the Board and File  2023139 was opened on &8203;September 7, 2023&8203;. 

A hearing on the Application was conducted on September 19, 2023 at 1:00 PM before the Fire Safety Code Board of Appeal and Review. 

After consideration of the application, the testimony of the witnesses and of the entire record presented to the Board, and after carefully reviewing such information, a motion was made by Commissioner Thornton and seconded by Commissioners ODonnell and Spaziani to grant the Applicant the relief as outlined herein.  The motion passed on a 10 to 0 vote. 

 
RECORD OF THE CASE 

 
The following documents are part of the administrative record for Appeal  2023139 and are pertinent to the decision rendered: 

 
Variance Application  2023139 dated &8203;September 6, 2023&8203; and filed on &8203;September 7, 2023&8203;. 

State Fire Marshals Office &8203;Plan Review&8203; Report dated &8203;September 6, 2023&8203;. 


EXHIBITS 

 
The following documents were presented at the September 19, 2023 hearing as exhibits: 

 
None. 

 
FINDINGS OF FACT 

 
Based on the testimony and evidence introduced at the hearing and a review of the administrative file, the Board makes the following Findings of Fact: 

 
The numbers of the determinations below correspond with those of the &8203;September 6, 2023&8203; &8203;plan review&8203; report compiled by the State Fire Marshals Office.  The above report was utilized by the Board, the Applicant and the State Fire Marshals Office during the September 19, 2023 hearing on this matter.  Accordingly, the Board hereby incorporates the &8203;September 6, 2023&8203; &8203;plan review&8203; report as its initial findings of fact.  Any modification of the Boards findings relating to this report, such as correction of a deficiency by the Applicant, shall be noted herein. 

The building is  1-story above grade building &8203;without&8203; a basement level, that will be classified as a day care (adult) occupancy, consisting of approximately three thousand six hundred forty-eight (3,648) square feet &8203;(gross area)&8203; and originally built in 1973. 

The building is of &8203;Type V (000)&8203; construction, will have a &8203;compliant&8203; total (complete) coverage fire alarm system and will not be provided with an &8203;approved&8203; automatic sprinkler system. 

There is no objection by the State Fire Marshals Office to the granting of the relief outlined herein. 

 
CONCLUSIONS OF LAW AND 

DETERMINATIONS ON VARIANCE REQUESTS 

 
References to NFPA shall mean the National Fire Protection Association; references to the Rhode Island Fire Code [RIFC] shall mean NFPA 1, (2018 edition) as incorporated by reference and amended by 450-RICR-00-00-7; and, references to the Rhode Island Life Safety Code [RILSC] shall mean NFPA 101, (2018 edition) as incorporated by reference and amended by 450-RICR-00-00-8. 

 
FIRE ALARM SYSTEM: The Board hereby directs the Applicant to comply with the provisions of RILSC sections 16.3.4.1 and 9.6.2.9 by providing the facility with an approved total (complete) coverage fire alarm system in accordance with section 9.6 throughout the facility, prior to occupancy, at the direction and to the satisfaction of the State Fire Marshals Office. 

FIRE ALARM SYSTEM: The Board hereby directs the Applicant to comply with the provisions of RILSC sections 16.3.4.1 and 9.6.5.5 by providing the fire alarm system of this facility with an approved key-operated drill switch, prior to occupancy, at the direction and to the satisfaction of the State Fire Marshals Office. 

FIRE ALARM SYSTEM: The Board hereby grants the Applicant a variance from the provisions of RILSC section 16.3.4.4.1 by waiving the requirement for fire alarm system emergency forces notification.  In granting this relief, the Board acknowledges that the facility will accommodate less than nineteen (19) [highly functional] clients, is located on the ground floor and that the occupiable area exceeds the three thousand (3,000) square foot threshold by a de minimis amount of only two hundred ten (210) square feet. 

 
Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Applicant.  The term approved, as used herein, is understood to mean in accordance with the specific provisions related to the particular subject as are contained in this Code, or as approved in particular by the Authority Having Jurisdiction (State Fire Marshal, his or her designated Deputy State Fire Marshals and/or Assistant Deputy State Fire Marshals). 

 
STATUS OF DECISION AND APPEAL RIGHTS 

 
This Decision constitutes a final order of the Fire Safety Code Board of Appeal and Review as set forth in RIGL section 42-35-12 and represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicants timely and continued compliance with all of the directives of the Board.  Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board.  [See: Fire Safety Code [FSC] section 450-RICR-00-00-1.7.2(W)]. 

Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  [See: FSC section 450-RICR-00-00-1.7.2(Y)].  In the event of complete, timely and continued compliance with the full Decision of the Board, the above-cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the FSC or a revision of the above-cited classification.  [See: FSC section 450-RICR-00-00-1.7.2(Z)]. 

Such changes in use or occupancy of this facility, or failure to continually comply with the Boards Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in RIGL section 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.  [See:  FSC section 450-RICR-00-00-1.7.2(AA)]. 

In accordance with RIGL section 23-28.3-5(e), any person who violates a final order of the Board may be subject to prosecution in the District Court with possible imprisonment for a term not exceeding one (1) year, or fined not more than one thousand dollars (1000) for each offense. 

In accordance with RIGL section 42-35-12, the Applicant may appeal the Boards Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth Division of the District Court.  [See: RIGL section 23-28.3-6 and FSC section 450-RICR-00-00-1.7.2(S)].  Commencement of such an action does not operate as an automatic stay of this Decision [See: RIGL section 42-35-15(c)].
rhode island coat of arms A Rhode Island Government Web site