Fire Safety Code, Rhode Island

Decisions - Details

STATE OF RHODE ISLAND
(401) 889-5551 phone
(401) 889-5279 fax
711 TTY
FIRE SAFETY CODE - BOARD OF APPEAL AND REVIEW
560 Jefferson Boulevard
Suite 202
Warwick, RI 02886
DECISION
FILE NO.: 2023107
LOCATION OF PREMISES: 99 Nooseneck Hill Road, West Greenwich, RI
APPLICANT: Mohamed Ganchi 99 Nooseneck Hill Road West Greenwich, RI 02817
USE OR OCCUPANCY: Hotels and Dormitories
DATE OF DECISION: 2023-12-06
As documented in the file, a hearing involving the above-captioned property was conducted on Tuesday, November 7, 2023 before the Fire Safety Code Board of Appeal and Review [hereinafter the Board], pursuant to Rhode Island General Laws [RIGL] sections 23-28.3-5, 42-35-9 and 42-46-3. 


In attendance at the hearing were the following: 

COMMISSIONERS: Chairman Newbrook, Vice-Chairman Blackburn and Commissioners Pearson, Sylvester, Booth, Thornton, ODonnell and Muto. 

AUTHORITY HAVING JURISDICTION [AHJ]:  State Fire Marshal Michael DeRosa of the West Greenwich Fire Marshals Office. 

APPLICANT: Mohamed Ganchi. 

EXECUTIVE DIRECTOR: W. Keith Burlingame, Esq. 


TRAVEL OF THE CASE 

 
This is an Application for Variance filed under RIGL chapter 23-28.3, entitled Fire Safety Code Board of Appeal and Review, and the Administrative Regulations promulgated thereunder. 

The Application was filed by Mohamed Ganchi (&8203;owner&8203;) of 99 Nooseneck Hill Road, West Greenwich, RI dated &8203;June 24, 2023&8203;. 

The Application was received by the Board and File  2023107 was opened on &8203;June 30, 2023&8203;. 

A hearing on the Application was conducted on November 7, 2023 at 1:00 PM before the Fire Safety Code Board of Appeal and Review. 

After consideration of the application, the testimony of the witnesses and of the entire record presented to the Board, and after carefully reviewing such information, a motion was made by Vice-Chairman Blackburn and seconded by Commissioner Sylvester to grant the Applicant the relief as outlined herein.  The motion passed on an 8 to 0 vote. 

 
RECORD OF THE CASE 

 
The following documents are part of the administrative record for Appeal  2023107 and are pertinent to the decision rendered: 

 
Variance Application  2023107 dated &8203;June 24, 2023&8203; and filed on &8203;June 30, 2023&8203;. 

West Greenwich Fire Marshals Office &8203;Inspection&8203; Report dated &8203;February 10, 2023&8203;. 

West Greenwich Compliance Order dated March 22, 2023. 

Reschedule Notice dated September 5, 2023. 


EXHIBITS 


The following documents were presented at the November 7, 2023 hearing as exhibits: 

 
None. 

 
FINDINGS OF FACT 

 
Based on the testimony and evidence introduced at the hearing and a review of the administrative file, the Board makes the following Findings of Fact: 

 
The numbers of the determinations below correspond with those of the &8203;February 10, 2023&8203; &8203;inspection&8203; report compiled by the West Greenwich Fire Marshals Office.  The above report was utilized by the Board, the Applicant and the West Greenwich Fire Marshals Office during the November 7, 2023 hearing on this matter.  Accordingly, the Board hereby incorporates the &8203;February 10, 2023&8203; &8203;inspection&8203; report as its initial findings of fact.  Any modification of the Boards findings relating to this report, such as correction of a deficiency by the Applicant, shall be noted herein. 

The building is  2-story above grade building &8203;without&8203; a basement level, classified as a motel (56 rooms) occupancy, consisting of approximately thirty-four thousand eight hundred sixty-four (34,864) square feet &8203;(living area)&8203; and originally built in 1989. 

The building is of &8203;Type V (000)&8203; construction,  an &8203;approved (with deficiencies)&8203; fire alarm system with emergency forces notification and  not provided with an &8203;approved&8203; automatic sprinkler system. 

The Board finds and it is agreed to by the parties that Violations  1  16 and 18  26 have been or in the process of being corrected and only Violations  17 and 27 are the subject of the instant appeal. 

There is no objection by the West Greenwich Fire Marshals Office to the granting of the relief outlined herein. 


CONCLUSIONS OF LAW AND 

DETERMINATIONS ON VARIANCE REQUESTS 

 
References to NFPA shall mean the National Fire Protection Association; references to the Rhode Island Fire Code [RIFC] shall mean NFPA 1, (2018 edition) as incorporated by reference and amended by 450-RICR-00-00-7; and, references to the Rhode Island Life Safety Code [RILSC] shall mean NFPA 101, (2018 edition) as incorporated by reference and amended by 450-RICR-00-00-8. 

 
FIRE ALARM SYSTEM: The Board hereby grants the Applicant a time variance of six (6) months from the date of  to comply with the provisions of RILSC sections 29.3.4.1 and 29.3.4.3.4 by providing approved fire alarm system audible and visible notification signals in accordance with section 9.6 and NFPA 72 (2019) chapter 18 in the bathroom(s) by the fitness center, at the direction and to the satisfaction of the West Greenwich Fire Marshals Office. 

FIRE ALARM SYSTEM: The Board hereby grants the Applicant the time variance outlined in item 1 above to comply with the provisions of RILSC sections 29.3.4.1, 29.3.4.3.1 and 9.6.3 by providing the guest rooms of this facility with approved fire alarm system notification signals in accordance with section 9.6 and NFPA 72 (2019) chapter 18, at the direction and to the satisfaction of the West Greenwich Fire Marshal's Office, subject to the following provisions: 

Audible alarm signals shall be in accordance with NFPA 72 (2019) sections 18.4.1, 18.4.2 and 18.4.6; and, 

Visible alarm signals shall be in accordance with RILSC sections 29.3.4.3.3 and NFPA 72 (2019) sections 18.5 and 18.5.5.8. 

Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Applicant.  The term approved, as used herein, is understood to mean in accordance with the specific provisions related to the particular subject as are contained in this Code, or as approved in particular by the Authority Having Jurisdiction (State Fire Marshal, his or her designated Deputy State Fire Marshals and/or Assistant Deputy State Fire Marshals). 

 
The Board hereby authorizes the West Greenwich Fire Marshals Office, upon receiving a written request, to extend the above timeline(s) for good faith compliance efforts being demonstrated by the Applicant by one (1) or more extensions of time of not more than thirty (30) days each, for a period not to exceed ninety (90) days in accordance with the provisions of 450-RICR-00-00-1.7.2(X). 


Finally, the Board directs that upon the expiration of the above time variance(s) there shall be no further continuances or extensions relating to these violations considered or granted. 

 
STATUS OF DECISION AND APPEAL RIGHTS 

 
This Decision constitutes a final order of the Fire Safety Code Board of Appeal and Review as set forth in RIGL section 42-35-12 and represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicants timely and continued compliance with all of the directives of the Board.  Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board.  [See: Fire Safety Code [FSC] section 450-RICR-00-00-1.7.2(W)]. 

Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  [See: FSC section 450-RICR-00-00-1.7.2(Y)].  In the event of complete, timely and continued compliance with the full Decision of the Board, the above-cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the FSC or a revision of the above-cited classification.  [See: FSC section 450-RICR-00-00-1.7.2(Z)]. 

Such changes in use or occupancy of this facility, or failure to continually comply with the Boards Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in RIGL section 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.  [See:  FSC section 450-RICR-00-00-1.7.2(AA)]. 

In accordance with RIGL section 23-28.3-5(e), any person who violates a final order of the Board may be subject to prosecution in the District Court with possible imprisonment for a term not exceeding one (1) year, or fined not more than one thousand dollars (1000) for each offense. 

In accordance with RIGL section 42-35-12, the Applicant may appeal the Boards Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth Division of the District Court.  [See: RIGL section 23-28.3-6 and FSC section 450-RICR-00-00-1.7.2(S)].  Commencement of such an action does not operate as an automatic stay of this Decision [See: RIGL section 42-35-15(c)].