Fire Safety Code, Rhode Island

Decisions - Details

STATE OF RHODE ISLAND
(401) 889-5551 phone
(401) 889-5279 fax
711 TTY
FIRE SAFETY CODE - BOARD OF APPEAL AND REVIEW
560 Jefferson Boulevard
Suite 202
Warwick, RI 02886
DECISION
FILE NO.: 030028
LOCATION OF PREMISES: 299 Pocasset Avenue
APPLICANT: Mr. John Sebastianelli 60 Hyde Street Cranston, RI 02920
USE OR OCCUPANCY: Business
DATE OF DECISION: 2004-03-08
The above-captioned case was scheduled for hearing on October 7, 2003 at 1:00 P.M.  At that time, Acting Chairman Burlingame and Commissioners Wahlberg, Preiss, Newbrook, Pearson, Coutu and Filippi were present.  The fire service was represented by Assistant Deputy State Fire Marshal Daniel Isles of the Providence Fire Marshal’s Office.  A motion was made by Commissioner Newbrook and seconded by Commissioner Preiss to grant the Applicant relief as outlined herein.  The motion was unanimous.

FINDINGS OF FACT
	
The numbers of the Decision below correspond with those of a January 31, 2003 plan review report compiled by the Providence Fire Marshal’s Office.  The above report was utilized by the Board, the Applicant and the  Providence Fire Marshal’s Office during the October 7, 2003 hearing on this matter.  Accordingly, the Board hereby incorporates the January 31, 2003 plan review report as its initial findings of fact.  Any modification of the Board’s findings, such as correction of a deficiency by the Applicant, shall be noted herein. 
	
Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Applicant.  The term “approved”, as used herein, is defined in section 23-28.1-4(3) of the Rhode Island General Laws.

CONCLUSIONS AND VARIANCE REQUESTS
	
1.  The Board hereby grants a variance from the provisions of section 23-28.17-4 in order to allow the Applicant to maintain the existing stairs servicing the basement of this facility.  In granting this variance, it is the understanding of the Board that the basement shall remain unoccupied and shall be utilized only for utilities and storage and that the Providence Fire Marshal’s office has no objection.
	
2.  It is the understanding of the Board that the Applicant has corrected deficiency #2 by providing both the front and rear stairwells with approved handrails at the direction and to the satisfaction of the Providence Fire Marshal’s office.
	
3.  The Board hereby grants a variance from the provisions of section 23-28.17-2 in order to allow the Applicant to maintain the basement of this facility with only a single means of egress.  In granting this variance, it is the understanding and direction of the Board that the basement shall not be occupied.  Further, the Board directs the Applicant to provide the basement area with approved emergency lighting installed at the direction and to the satisfaction of the Providence Fire Marshal within 120 days of the date of this decision.
	
4.  The Board hereby directs the Applicant to correct deficiency #4 by providing the egress system of this facility with approved solid core doors maintaining an approximate fire rating of twenty (20) minutes.  The above doors shall be further equipped with spring loaded hinges installed at the direction and to the satisfaction of the Providence Fire Marshal within 120 days of the date of this decision.
	
5.  As a condition of the variances granted herein, the Board hereby directs the applicant to provide this facility with an approved local fire alarm system, installed at the direction and to the satisfaction of the Providence Fire Marshal and the Providence Division of Telecommunications, within 120 days of the date of this decision.
	
6.  As a condition of the variances granted herein, the Board hereby directs the Applicant to provide the boiler of this facility with an approved domestically supplied sprinkler head, and to further provide the boiler with an approved remote shut off switch, at the direction and to the satisfaction of the Providence Fire Marshal within 120 days of the date of this decision.

STATUS OF DECISION AND APPEAL RIGHTS
	
This Decision represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicant’s timely and continued compliance with all of the directives of the Board.  Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board. (See:  Board Rules and Regulations, section 6-2-17).
	
Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  (See: Board Rules and Regulations, section 6-2-18.)  In the event of complete, timely and continued compliance with the full Decision of the Board, the above cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the Fire Code or a revision of the above-cited classification.  (See: Board Rules and Regulations, section 6-2-19).  

Such changes in use or occupancy of this facility, or failure to continually comply with the Board’s Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in R.I.G.L. 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.  (See: Board Rules and Regulations, section 6-2-20).
	
The Applicant may appeal the Board’s Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth division of the District Court.  Commencement of such an action does not operate as an automatic stay of this Decision [R.I.G.L. 42-35-15(c)].