FIRE SAFETY CODE - BOARD OF APPEAL AND REVIEW
560 Jefferson Boulevard
Suite 202
Warwick, RI 02886
DECISION
FILE NO.: 200310
LOCATION OF PREMISES: 79 Verdi Street
APPLICANT: Ms. Nancy Dias 1177 Greenwich Avenue Warwick, R.I. 02886
USE OR OCCUPANCY: Apartment
DATE OF DECISION: 2003-04-24
The above-captioned case was scheduled for hearing on January 30, 2001 at 1:30 P.M. At that time, Chairman Farrell and Commissioners Wahlberg, Newbrook, O'Connell, Richard, Pearson, Burlingame and Coutu were present.  The fire service was represented by Assistant Deputy State Fire Marshal David P. Vartian of the North Providence Fire Marshal’s Office.  A motion was made by Commissioner Newbrook and seconded by Commissioner Coutu to grant the Applicant relief as outlined herein.  The motion was unanimous.

FINDINGS OF FACT
	
The numbers of the Decision below correspond with those of a November 29, 2000 inspection report complied by the North Providence Fire Marshal’s Office.  The above report was utilized by the Board, the Applicant and the North Providence Fire Marshal’s Office during the January 30, 2001 hearing on this matter.  Accordingly, the Board hereby incorporates the report as its initial findings of fact.  Any modification of the Board’s findings, such as correction of a deficiency by the Applicant, shall be noted herein. 
	
Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Applicant.  The term “approved”, as used herein, is defined in section 23-28.1-4(3) of the Rhode Island General Laws.

CONCLUSIONS AND VARIANCE REQUESTS

1. It is the understanding of the Board that the Applicant has corrected deficiency 1, by providing this facility with approved fire alarm system, installed at the direction and to the satisfaction of the North Providence Fire Marshal.

2. The Board hereby grants a variance from the provisions of section 23-28.16-5 in order to allow the Applicant to maintain the existing plaster wall construction and rating of the stairways of this facility.  It is the understanding of the Board that the Applicant has corrected the remainder of deficiency 2 by providing the cited stairs with approved handrails.

3. The Board hereby grants a variance from the provisions of section 23-28.16-6 in order to allow the Applicant to maintain the existing swing of the cited doors and to provide the existing egress door jambs of this facility with approved solid core wood doors having an approximate fire rating of twenty minutes.  The above doors shall be equipped with spring-loaded hinges and installed, at the direction and to the satisfaction of the North Providence Fire Marshal within 120 days of the date of this decision.

4. The Board hereby grants a variance from the provisions of section 23-28.9-1 & 2, in order to allow the Applicant to provide a domestically supplied sprinkler head over the boiler of this facility.  The above sprinkler head shall be installed at the direction and to the satisfaction of the North Providence Fire Marshal within 120 days of the date of this decision.

5. It is the understanding of the Board that the Applicant has corrected deficiency 5 by providing this facility with approved fire extinguishers at the direction and to the satisfaction of the North Providence Fire Marshal's office.

6. It is the understanding of the Board that the Applicant has corrected deficiency 6 by providing this facility with approved exit signs at the direction and to the satisfaction of the North Providence Fire Marshal.

STATUS OF DECISION AND APPEAL RIGHTS
	
This Decision represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicant’s timely and continued compliance with all of the directives of the Board. Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board. (See: Board Rules and Regulations, section 6-2-17).
	
Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein. (See: Board Rules and Regulations, section 6-2-18)  In the event of complete, timely and continued compliance with the full Decision of the Board, the above cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the Fire Code or a revision of the above-cited classification. (See: Board Rules and Regulations, section 6-2-19).  

Such changes in use or occupancy of this facility, or failure to continually comply with the Board’s Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in R.I.G.L. 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy. (See: Board Rules and Regulations, section 6-2-20).
	
The Applicant may appeal the Board’s Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth division of the District Court.  Commencement of such an action does not operate as an automatic stay of this Decision [R.I.G.L. 42-35-15(c)].

This decision was mailed on 2-08-01.