Fire Safety Code, Rhode Island

Decisions - Details

STATE OF RHODE ISLAND
(401) 889-5551 phone
(401) 889-5279 fax
711 TTY
FIRE SAFETY CODE - BOARD OF APPEAL AND REVIEW
560 Jefferson Boulevard
Suite 202
Warwick, RI 02886
DECISION
FILE NO.: 010045
LOCATION OF PREMISES: 139 Atwood Avenue
APPLICANT: Alexandre Pinto 65 Elder Street Pawtucket, RI 02860
USE OR OCCUPANCY: Apartment
DATE OF DECISION: 2003-01-13
The above captioned case was scheduled for hearing on August 2l, 2001 at l:30 p.m.  At that time a subcommittee of the Board reviewed the Applicants request.  The Subcommittees Recommendation was subsequently approved during an August 28, 2001 full hearing of the Board.  At that time, Chairman Farrell and Commissioners Coutu, Evans, Filippi, Wahlberg, OConnell and Burlingame were present.   A motion was made by Commissioner Coutu and seconded by Commissioner Evans to grant the Applicant relief as outlined herein.  The motion was unanimous.

FINDING OF FACT
	
The numbers of the Decision below correspond with those of a January 3l, 2001 inspection report compiled by the Pawtucket Fire Marshals Office.  The above report was utilized by the Board, the Applicant and the Pawtucket Fire Marshal during the August 2l, 2001 hearing on this matter.  Accordingly, the Board hereby incorporates the January 3l, 2001 inspection report as its initial findings of fact.
	Any deficiency, understood by the Board, to have been corrected which is not so corrected shall be immediately corrected by the Applicant.  The term approved as used 
herein is defined in Section 23-28.l-4(3) of the Rhode Island General Laws.

CONCLUSIONS AND VARIANCE REQUESTS

1.	The Board hereby grants a variance from the provisions of Section 23-28.l6-2 in order to allow the Applicant to maintain the existing egress system of this facility as modified herein.  In granting this variance, it is the understanding of the Board that the Pawtucket Fire Marshals Office has no objection in light of the Applicants agreement to provide this facility with an approved fire alarm system as outlined in item 9 below.

2.	The Board hereby grants a variance from the provisions of Section 23-28.l6-3 in order to allow the Applicant to maintain access to the interior stairways through kitchens.  During the August 2l, 2001 hearing on this matter.  The Board was advised that there were no fire escapes accessed by the bedrooms.  Finally, the Board hereby grants a variance from the above provisions in order to allow the Applicant to provide the existing apartment door jambs of this facility with approved solid core wood doors maintaining an approximate fire rating of twenty (20) minutes, installed with spring-loaded hinges.  The above doors and hinges shall be installed at the direction and to the satisfaction of the Pawtucket Fire Marshal within one hundred and twenty (l20) days from the date of this Decision.

3.	The Board hereby grants a variance from the provisions of Section 23-28.l6-3 in order to allow the Applicant to maintain the existing construction rating of the cited stairways of this facility as modified herein.

4.	The Board hereby grants a variance from the provisions of Section 23-28.l6-6 in order to allow the Applicant to maintain the existing swing of the cited exit door.  The Board further grants a variance from the above provisions in order to allow the Applicant to provide the other egress system doors with approved spring-loaded hinges as outlined in item 2 above.

5.	The Board hereby directs the Applicant to correct deficiency 5 by providing this facility with approved fire stopping, at the direction and to the satisfaction of the Pawtucket Fire Marshal, within one hundred and twenty (l20) days from the date of this Decision.

6.	As a condition of the variances granted herein, the Board hereby directs the Applicant to provide this facility with approved group type A externally illuminated exit signs, installed at the direction and to the satisfaction of the Pawtucket Fire Marshal, within one hundred and twenty (l20) days from the date of this Decision.

7.	As a condition of the variances granted herein, the Board hereby directs the Applicant to provide this facility with approved emergency lighting, installed at the direction and to the satisfaction of the Pawtucket Fire Marshal, within one hundred and twenty (l20) days from the date of this Decision.

8.	The Board hereby grants a variance from the provisions of Section 23-28.l6-l3 and NFPA Standard l0, l988 edition in order to allow the Applicant the option of either providing each apartment unit with an approved fire extinguisher or providing this facility with fire extinguishers in accordance with the provisions of NFPA Standard l0, l988 edition.  In any event, the fire extinguishers shall be installed within fifteen (l5) days from the date of this Decision.

9.	As a condition of the variances granted herein, the Board hereby directs the Applicant to provide this facility with an approved local fire alarm, installed at the direction and to the satisfaction of the Pawtucket Fire Marshal or designee, in accordance with the provisions of Section 23-28.25-4(a), within one hundred and twenty (l20) days from the date of this Decision.

This Decision represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Applicants timely and continued compliance with all of the directives of the Board.  Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board.

Failure of the Applicant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  In the event of complete, timely and continued compliance with the full Decision of the Board, the above-cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the Fire Code or a revision of the above-cited classification.  Such changes in use or occupancy of this facility, or failure to continually comply with the Boards Decision, shall void all variances granted under the above-cited use or occupancy.  If such changes creates a new use or occupancy as outlined in R.I.G.L. 23-28.l-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.

The Applicant may appeal the Boards Decision within thirty (30) days of the mailing date of this Decision, by requesting to be reheard before a quorum of the full Board.  Commencement of such an action does not operate as an automatic stay of this Decision.  [RIGL 42-35-l5(c)]
rhode island coat of arms A Rhode Island Government Web site