FILE NO.: 2024051
LOCATION OF PREMISES: 55 West Alumni Avenue (Burnside Hall), Kingston
University of Rhode Island - Kingston, RI
APPLICANT: Wade Palazini c/o Jensen Hughes
117 Metro Center Boulevard - Suite 1002
Warwick, RI 02886
USE OR OCCUPANCY: Mixed
DATE OF DECISION: 2024-06-05
A hearing involving the above-captioned properties was conducted on Tuesday, May 14, 2024 before the Fire Safety Code Board of Appeal and Review [hereinafter the Board], pursuant to Rhode Island General Laws [RIGL] sections 23-28.3-5, 42-35-9 and 42-46-3.
In attendance at the hearing were the following:
COMMISSIONERS: Commissioners Muto, Spaziani, Walsh, Horan & Mancini.
AUTHORITY HAVING JURISDICTION [AHJ]: Deputy State Fire Marshal Daniel Hultquist of the State Fire Marshals Office.
APPELLANT: Wade Palazini and Samuel Adams.
EXECUTIVE DIRECTOR: W. Keith Burlingame, Esq.
TRAVEL OF THE CASE
1. This is an Application for Appeal submitted under RIGL chapter 23-28.3, entitled Fire Safety Code Board of Appeal and Review, and the Administrative Regulations promulgated thereunder.
2. The Application was submitted by Wade Palazini (authorized representative) of Jensen Hughes, 117 Metro Center Boulevard Suite 1002, Warwick, RI dated April 9, 2024.
3. The Application was processed by the Board and Appeal 2024045-061 and 063-069 was filed on April 11, 2024.
4. The majority of these properties were previously before the Board on multiple days in 2011 and are subject to Decisions 110140 - 110165 issued on November 29, 2011 [Brookside Hall and Hillside Hall were not included in this Decision as they were not yet constructed at the time].
5. A hearing on the Application was conducted on May 14, 2024 at 1:00 PM before the Fire Safety Code Board of Appeal and Review.
6. After consideration of the application, the testimony of the witnesses and of the entire record presented to the Board, and after carefully reviewing such information, a motion was made by Commissioner Horan and seconded by Commissioner Spaziani to grant the Appellant the relief as outlined herein. The motion passed on a 5 to 0 vote.
RECORD OF THE CASE
The following documents are part of the administrative record for Appeal 2024045-061 and 063-069 and are pertinent to the decision rendered:
1. Appeal Application FVA-24-45 through FVA-24-61 and FVA-24-63 through FVA-24-69 submitted on April 9, 2024 and filed on April 11, 2024.
a. Attached Plan of Action dated May 7, 2024.
b. Letter of authorization for Jensen Hughes from Jeffrey Plouffe dated April 9, 2024.
2. State Fire Marshals Office Inspection Reports:
a. 2024045 Adams Hall LSI-23-391 9/1/23
b. 2024046 Aldrich Hall LSI-23-392 9/1/23
c. 2024047 Barlow Hall LSI-23-393 9/1/23
d. 2024048 Bressler Hall LSI-23-394 9/1/23
e. 2024049 Brookside Hall LSI-23-395 9/1/23
f. 2024050 Browning Hall LSI-23-396 9/1/23
g. 2024051 Burnside Hall LSI-23-397 9/1/23
h. 2024052 Butterfield Hall LSI-23-398 9/1/23
i. 2024053 Coddington Hall LSI-23-399 9/1/23
j. 2024054 Dorr Hall LSI-23-400 9/1/23
k. 2024055 Eddy Hall LSI-23-401 9/1/23
l. 2024056 Ellery Hall LSI-23-402 9/1/23
m. 2024057 Fayerweather Hall LSI-23-403 9/1/23
n. 2024058 Garrahy Hall LSI-23-404 8/9/23
o. 2024059 Gorham Hall LSI-23-405 9/1/23
p. 2024060 Heathman Hall LSI-23-406 9/1/23
q. 2024061 Hillside Hall LSI-23-407 9/1/23
r. 2024063 Hopkins Hall LSI-23-408 9/1/23
s. 2024064 Hutchinson Hall LSI-23-409 9/1/23
t. 2024065 Merrow Hall LSI-23-410 9/1/23
u. 2024066 Peck Hall LSI-23-411 9/1/23
v. 2024067 Tucker Hall LSI-23-413 9/1/23
w. 2024068 Weldin Hall LSI-23-415 9/1/23
x. 2024069 Wiley Hall LSI-23-417 9/1/23
EXHIBITS
The following documents were presented at the May 14, 2024 hearing as exhibits:
1. None.
FINDINGS OF FACT
Based on the testimony and evidence introduced at the hearing and a review of the administrative file, the Board makes the following Findings of Fact:
1. The determinations below correspond with the May 7, 2024 plan of action report compiled by the Applicant in response to the State Fire Marshals Office Life Safety Inspection Reports listed in 2(a) through (x) above. The above report was utilized by the Board, the Appellant and the State Fire Marshals Office during the May 14, 2024 hearing on this matter. Accordingly, the Board hereby incorporates by reference the May 7, 2024 plan of action report as its initial findings of fact. Any modification of the Boards findings relating to this report, such as correction of a deficiency by the Appellant, shall be noted herein.
2. Additionally, the Board directs that any violation or deficiency self-identified within the plan of action and addressed by this Decision shall be subject to correction and enforcement by the AHJ as if cited by the AHJ directly.
3. The Board finds through the testimony of the Appellant that of the approximate one hundred ninety-five (195) violations identified in the plan of action, one hundred fifty-five (155) have been corrected.
4. The Board further finds through the testimony of the Appellant that as of May 19, 2024 all of these residential properties with the exception of Brookside Hall will be vacant for the summer break and not again occupied until the start of the 2024/2025 academic year.
5. There is no objection by the State Fire Marshals Office to the granting of the relief outlined herein.
CONCLUSIONS OF LAW AND
DETERMINATIONS ON VARIANCE REQUESTS
References to NFPA shall mean the National Fire Protection Association; references to the Rhode Island Fire Code [RIFC] shall mean NFPA 1, (2018 edition) as incorporated by reference and amended by 450-RICR-00-00-7; and, references to the Rhode Island Life Safety Code [RILSC] shall mean NFPA 101, (2018 edition) as incorporated by reference and amended by 450-RICR-00-00-8.
1. The Board hereby grants the Appellant a time variance of fourteen (14) days from the date of the decision to correct all outstanding deficiencies/violations in all buildings relating to the non-compliant storage of combustibles and relating to non-compliant electrical wiring, fixtures and/or appliances, at the direction and to the satisfaction of the State Fire Marshals Office.
2. The Board hereby grants the Appellant a time variance of sixty (60) days from the date of the decision to correct all other outstanding deficiencies/violations in all buildings with the exception of those relating to guard configuration, at the direction and to the satisfaction of the State Fire Marshals Office.
3. The Board hereby grants the Appellant a time variance of two (2) years from the date of the decision to correct all outstanding guard configuration deficiencies/violations in all buildings (except as noted below), at the direction and to the satisfaction of the State Fire Marshals Office.
a. The following eleven (11) buildings are exempted from this requirement as previous Board relief has been granted in the 2011 Decision: Aldrich, Barlow, Bressler, Browning, Burnside, Butterfield, Coddington, Dorr, Ellery, Hopkins and Weldin.
Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Appellant. The term approved, as used herein, is understood to mean in accordance with the specific provisions related to the particular subject as are contained in this Code, or as approved in particular by the Authority Having Jurisdiction (State Fire Marshal, his or her designated Deputy State Fire Marshals and/or Assistant Deputy State Fire Marshals).
STATUS OF DECISION AND APPEAL RIGHTS
1. This Decision constitutes a final order of the Fire Safety Code Board of Appeal and Review as set forth in RIGL section 42-35-12 and represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy. Accordingly, every variance granted is conditioned upon the Appellants timely and continued compliance with all of the directives of the Board. Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board. [See: Fire Safety Code [FSC] section 450-RICR-00-00-1.7.2(W)].
2. Failure of the Appellant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein. [See: FSC section 450-RICR-00-00-1.7.2(Y)]. In the event of complete, timely and continued compliance with the full Decision of the Board, the above-cited variances shall be deemed to have vested in the above-captioned facility. As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the FSC or a revision of the above-cited classification. [See: FSC section 450-RICR-00-00-1.7.2(Z)].
3. Such changes in use or occupancy of this facility, or failure to continually comply with the Boards Decision shall void all variances granted under the above-cited use or occupancy. If such change creates a new use or occupancy as outlined in RIGL section 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy. [See: FSC section 450-RICR-00-00-1.7.2(AA)].
4. In accordance with RIGL section 23-28.3-5(e), any person who violates a final order of the Board may be subject to prosecution in the District Court with possible imprisonment for a term not exceeding one (1) year, or fined not more than one thousand dollars (1000) for each offense.
5. In accordance with RIGL section 42-35-12, the Appellant may appeal the Boards Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth Division of the District Court. [See: RIGL section 23-28.3-6 and FSC section 450-RICR-00-00-1.7.2(S)]. Commencement of such an action does not operate as an automatic stay of this Decision [See: RIGL section 42-35-15(c)].