Fire Safety Code, Rhode Island

Decisions - Details

STATE OF RHODE ISLAND
(401) 889-5551 phone
(401) 889-5279 fax
711 TTY
FIRE SAFETY CODE - BOARD OF APPEAL AND REVIEW
560 Jefferson Boulevard
Suite 202
Warwick, RI 02886
DECISION
FILE NO.: 2024110
LOCATION OF PREMISES: 502 Broadway, Pawtucket, RI
APPLICANT: Peter Casale 250 Gano Street - Suite 1 Providence, RI 02906
USE OR OCCUPANCY: Mercantile
DATE OF DECISION: 2024-08-21
A hearing involving the above-captioned property was conducted on Tuesday, August 6, 2024 before the Fire Safety Code Board of Appeal and Review [hereinafter the Board], pursuant to Rhode Island General Laws [RIGL] sections 23-28.3-5, 42-35-9 and 42-46-3.

	In attendance at the hearing were the following:
COMMISSIONERS: Acting Chair Blackburn and Commissioners Thornton, ODonnell, Spaziani, Walsh, Horan & Mancini.
AUTHORITY HAVING JURISDICTION [AHJ]: Assistant Deputy State Fire Marshal R. Will Maher of the Pawtucket Fire Marshals Office.
APPELLANT: Peter Casale, Olivia Casale and David Sisson.
EXECUTIVE DIRECTOR: W. Keith Burlingame, Esq.

TRAVEL OF THE CASE

1.	This is an Application for Appeal submitted under RIGL chapter 23-28.3, entitled Fire Safety Code Board of Appeal and Review, and the Administrative Regulations promulgated thereunder.
2.	The Application was submitted by Peter Casale (authorized representative) of 250 Gano Street  Suite 1, Providence, RI dated June 28, 2024.
3.	The Application was processed by the Board and Appeal  2024110 was filed on July 3, 2024.
4.	A hearing on the Application was conducted on August 6, 2024 at 1:00 PM before the Fire Safety Code Board of Appeal and Review.
5.	After consideration of the application, the testimony of the witnesses and of the entire record presented to the Board, and after carefully reviewing such information, a motion was made by Commissioner Mancini and seconded by Commissioner Walsh to grant the Appellant the relief as outlined herein.  The motion passed on a 7 to 0 vote.

RECORD OF THE CASE

The following documents are part of the administrative record for Appeal  2024110 and are pertinent to the decision rendered:

1.	Appeal Application  FVA-24-110 submitted on June 28, 2024 and filed on July 3, 2024.
a.	Letter of authorization for Peter Casale from Paul Griesinger dated July 2, 2024.
2.	Pawtucket Fire Marshals Office Inspection Report dated May 20, 2024.

EXHIBITS

The following documents were presented at the August 6, 2024 hearing as exhibits:

1.	None.

FINDINGS OF FACT

	Based on the testimony and evidence introduced at the hearing and a review of the administrative file, the Board makes the following Findings of Fact:

1.	The numbers of the determinations below correspond with those of the May 20, 2024 inspection report compiled by the Pawtucket Fire Marshals Office.  The above report was utilized by the Board, the Appellant and the Pawtucket Fire Marshals Office during the August 6, 2024 hearing on this matter.  Accordingly, the Board hereby incorporates the May 20, 2024 inspection report as its initial findings of fact.  Any modification of the Boards findings relating to this report, such as correction of a deficiency by the Appellant, shall be noted herein.
2.	The building is an existing 1-story above grade building with a basement level, classified as a mercantile occupancy, consisting of approximately eighteen thousand three hundred (18,300) square feet (gross area) and originally built in 1978.
3.	The building is of Type III (200) construction, has a compliant fire alarm system and is not provided with an approved automatic sprinkler system.
4.	The Board finds through the testimony of the Appellant that the basement level is not occupied and is utilized for utilities and maintenance only and that the first-floor mercantile tenant has no access to this level.
5.	There is no objection by the Pawtucket Fire Marshals Office to the granting of the relief outlined herein.

CONCLUSIONS OF LAW AND
DETERMINATIONS ON VARIANCE REQUESTS

References to NFPA shall mean the National Fire Protection Association; references to the Rhode Island Fire Code [RIFC] shall mean NFPA 1, (2018 edition) as incorporated by reference and amended by 450-RICR-00-00-7; and, references to the Rhode Island Life Safety Code [RILSC] shall mean NFPA 101, (2018 edition) as incorporated by reference and amended by 450-RICR-00-00-8.

1.	This deficiency/violation has been corrected.
2.	This deficiency/violation has been corrected.
3.	This deficiency/violation has been corrected.
4.	The Board hereby grants the Appellant a time variance of thirty (30) days from the date of the decision to comply with the provisions of RILSC sections 37.3.4.1 and 9.6.2.11 by providing the basement of this facility with compliant fire detection, at the direction and to the satisfaction of the Pawtucket Fire Marshals Office.
5.	This deficiency/violation has been corrected.
6.	This deficiency/violation has been corrected.
7.	This deficiency/violation has been corrected.
8.	This deficiency/violation has been corrected.
9.	This deficiency/violation has been corrected.
10.	No longer a violation provided that the basement level remains unoccupied.
11.	No longer a violation provided that the basement level remains unoccupied.

Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Appellant.  The term approved, as used herein, is understood to mean in accordance with the specific provisions related to the particular subject as are contained in this Code, or as approved in particular by the Authority Having Jurisdiction (State Fire Marshal, his or her designated Deputy State Fire Marshals and/or Assistant Deputy State Fire Marshals).

STATUS OF DECISION AND APPEAL RIGHTS

1.	This Decision constitutes a final order of the Fire Safety Code Board of Appeal and Review as set forth in RIGL section 42-35-12 and represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Appellants timely and continued compliance with all of the directives of the Board.  Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board.  [See: Fire Safety Code [FSC] section 450-RICR-00-00-1.7.2(W)].
2.	Failure of the Appellant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  [See: FSC section 450-RICR-00-00-1.7.2(Y)].  In the event of complete, timely and continued compliance with the full Decision of the Board, the above-cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the FSC or a revision of the above-cited classification.  [See: FSC section 450-RICR-00-00-1.7.2(Z)].
3.	Such changes in use or occupancy of this facility, or failure to continually comply with the Boards Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in RIGL section 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.  [See:  FSC section 450-RICR-00-00-1.7.2(AA)].
4.	In accordance with RIGL section 23-28.3-5(e), any person who violates a final order of the Board may be subject to prosecution in the District Court with possible imprisonment for a term not exceeding one (1) year, or fined not more than one thousand dollars (1000) for each offense.
5.	In accordance with RIGL section 42-35-12, the Appellant may appeal the Boards Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth Division of the District Court.  [See: RIGL section 23-28.3-6 and FSC section 450-RICR-00-00-1.7.2(S)].  Commencement of such an action does not operate as an automatic stay of this Decision [See: RIGL section 42-35-15(c)].
rhode island coat of arms A Rhode Island Government Web site