FILE NO.: 2024200
LOCATION OF PREMISES: 635 Ocean Road, Narragansett, RI
APPLICANT: Brian Sullivan
635 Ocean Road
Narragansett, RI 02882
USE OR OCCUPANCY: Mixed
DATE OF DECISION: 2025-01-29
A hearing involving the above-captioned property was conducted on Tuesday, January 14, 2025 before the Fire Safety Code Board of Appeal and Review [hereinafter the Board], pursuant to Rhode Island General Laws [RIGL] sections 23-28.3-5, 42-35-9 and 42-46-3.
In attendance at the hearing were the following:
COMMISSIONERS: Vice-Chairperson Thornton and Commissioners Spaziani, ODonnell, Muto, Walsh, Horan & Mancini.
AUTHORITY HAVING JURISDICTION [AHJ]: Deputy State Fire Marshal William Leahy of the State Fire Marshals Office.
APPELLANT: Brian Sullivan and Wade Palazini.
EXECUTIVE DIRECTOR: W. Keith Burlingame, Esq.
TRAVEL OF THE CASE
1. This is an Application for Appeal submitted under RIGL chapter 23-28.3, entitled Fire Safety Code Board of Appeal and Review, and the Administrative Regulations promulgated thereunder.
2. The Application was submitted by Brian Sullivan (authorized representative) of 635 Ocean Road, Narragansett, RI dated November 4, 2024.
3. The Application was processed by the Board and Appeal 2024200 was filed on November 4, 2024.
4. The property was previously before the Board on or about July 30, 2024 at which time Decision 2024107 was issued dated August 8, 2024.
5. A hearing on the Application was conducted on January 14, 2025 at 1:00 PM before the Fire Safety Code Board of Appeal and Review.
6. After consideration of the application, the testimony of the witnesses and of the entire record presented to the Board, and after carefully reviewing such information, a motion was made by Commissioner Horan and seconded by Commissioner Walsh to grant the Appellant the relief as outlined herein. The motion passed on a 7 to 0 vote.
RECORD OF THE CASE
The following documents are part of the administrative record for Appeal 2024200 and are pertinent to the decision rendered:
1. Appeal Application FVA-24-200 submitted on November 4, 2024 and filed on November 4, 2024.
a. Attached Plan of Action dated November 1, 2024
b. Letter of authorization for Brian Sullivan from Br. Michael Shubnell dated June 20, 2024.
2. State Fire Marshals Office Inspection Report dated May 23, 2024.
3. Decision 2024107 dated August 8, 2024.
EXHIBITS
The following documents were presented at the January 14, 2025 hearing as exhibits:
1. None.
FINDINGS OF FACT
Based on the testimony and evidence introduced at the hearing and a review of the administrative file, the Board makes the following Findings of Fact:
1. The determinations below correspond with the November 1, 2024 plan of action report compiled by the Appellant and Decision 2024107. The above report was utilized by the Board, the Appellant and the State Fire Marshals Office during the January 14, 2025 hearing on this matter. Accordingly, the Board hereby incorporates the November 1, 2024 plan of action report as its initial findings of fact. Any modification of the Boards findings relating to this report, such as correction of a deficiency by the Appellant, shall be noted herein.
2. The Board hereby reaffirms and incorporates by reference Decision 2024107 dated August 8, 2024 and all associated timelines.
3. There is no objection by the State Fire Marshals Office to the granting of the relief outlined herein.
CONCLUSIONS OF LAW AND
DETERMINATIONS ON VARIANCE REQUESTS
References to NFPA shall mean the National Fire Protection Association; references to the Rhode Island Fire Code [RIFC] shall mean NFPA 1, (2018 edition) as incorporated by reference and amended by 450-RICR-00-00-7; and, references to the Rhode Island Life Safety Code [RILSC] shall mean NFPA 101, (2018 edition) as incorporated by reference and amended by 450-RICR-00-00-8.
1. This deficiency/violation has been corrected.
2. WINDOWS FOR RESCUE: Will comply in accordance with Decision 2024107 Item 2.
3. WINDOWS FOR RESCUE: The Board hereby grants the Appellant a variance from the provisions of RILSC section 15.2.11.1.2(1) by approving a partial automatic sprinkler system for the educational building in accordance with the Appellants plan of action [Appendix A] and Decision 2024107 Item 3.
Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Appellant. The term approved, as used herein, is understood to mean in accordance with the specific provisions related to the particular subject as are contained in this Code, or as approved in particular by the Authority Having Jurisdiction (State Fire Marshal, his or her designated Deputy State Fire Marshals and/or Assistant Deputy State Fire Marshals).
STATUS OF DECISION AND APPEAL RIGHTS
1. This Decision constitutes a final order of the Fire Safety Code Board of Appeal and Review as set forth in RIGL section 42-35-12 and represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy. Accordingly, every variance granted is conditioned upon the Appellants timely and continued compliance with all of the directives of the Board. Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board. [See: Fire Safety Code [FSC] section 450-RICR-00-00-1.7.2(W)].
2. Failure of the Appellant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein. [See: FSC section 450-RICR-00-00-1.7.2(Y)]. In the event of complete, timely and continued compliance with the full Decision of the Board, the above-cited variances shall be deemed to have vested in the above-captioned facility. As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the FSC or a revision of the above-cited classification. [See: FSC section 450-RICR-00-00-1.7.2(Z)].
3. Such changes in use or occupancy of this facility, or failure to continually comply with the Boards Decision shall void all variances granted under the above-cited use or occupancy. If such change creates a new use or occupancy as outlined in RIGL section 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy. [See: FSC section 450-RICR-00-00-1.7.2(AA)].
4. In accordance with RIGL section 23-28.3-5(e), any person who violates a final order of the Board may be subject to prosecution in the District Court with possible imprisonment for a term not exceeding one (1) year, or fined not more than one thousand dollars (1000) for each offense.
5. In accordance with RIGL section 42-35-12, the Appellant may appeal the Boards Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth Division of the District Court. [See: RIGL section 23-28.3-6 and FSC section 450-RICR-00-00-1.7.2(S)]. Commencement of such an action does not operate as an automatic stay of this Decision [See: RIGL section 42-35-15(c)].