Fire Safety Code, Rhode Island

Decisions - Details

STATE OF RHODE ISLAND
(401) 889-5551 phone
(401) 889-5279 fax
711 TTY
FIRE SAFETY CODE - BOARD OF APPEAL AND REVIEW
560 Jefferson Boulevard
Suite 202
Warwick, RI 02886
DECISION
FILE NO.: 2025043
LOCATION OF PREMISES: 825 Plainfield Street, Providence, RI
APPLICANT: Luca Ialongo c/o Jensen Hughes 117 Metro Central Boulevard, Suite1002 Warwick, RI 02886
USE OR OCCUPANCY: Apartment
DATE OF DECISION: 2025-05-22
A hearing involving the above-captioned property was conducted on Tuesday, May 6, 2025 before the Fire Safety Code Board of Appeal and Review [hereinafter the Board], pursuant to Rhode Island General Laws [RIGL] sections 23-28.3-5, 42-35-9 and 42-46-3.

	In attendance at the hearing were the following:
COMMISSIONERS: Vice-Chairperson Thornton and Commissioners Spaziani, Walker, Walsh & Horan.
AUTHORITY HAVING JURISDICTION [AHJ]: Assistant Deputy State Fire Marshal April Kuzdeba of the Providence Fire Marshals Office.
APPELLANT: Luca Ialongo and Wade Palazini.
EXECUTIVE DIRECTOR: W. Keith Burlingame, Esq.


TRAVEL OF THE CASE

1.	This is an Application for Appeal submitted under RIGL chapter 23-28.3, entitled Fire Safety Code Board of Appeal and Review, and the Administrative Regulations promulgated thereunder.
2.	The Application was submitted by Luca Ialongo (authorized representative) of Jensen Hughes, 117 Metro Center Boulevard  Suite 1002, Warwick, RI dated March 28, 2025.
3.	The Application was processed by the Board and Appeal  2025043 was filed on April 1, 2025.
4.	A hearing on the Application was conducted on May 6, 2025 at 1:00 PM before the Fire Safety Code Board of Appeal and Review.
5.	After consideration of the application, the testimony of the witnesses and of the entire record presented to the Board, and after carefully reviewing such information, a motion was made by Commissioner Horan and seconded by Commissioner Walsh to grant the Appellant the relief as outlined herein.  The motion passed on a 5 to 0 vote.

RECORD OF THE CASE

The following documents are part of the administrative record for Appeal  2025043 and are pertinent to the decision rendered:

1.	Appeal Application  FVA-25-43 submitted on March 28, 2025 and filed on April 1, 2025.
a.	Attached Plan of Action dated January 28, 2025.
b.	Letter of authorization for Jensen Hughes from Josh Barrett of Preservation of Affordable Housing, Inc. dated March 27, 2025.
2.	Providence Fire Marshals Office plan of action Report dated March 6, 2025.

EXHIBITS

The following documents were presented at the May 6, 2025 hearing as exhibits:

1.	None.

FINDINGS OF FACT

	Based on the testimony and evidence introduced at the hearing and a review of the administrative file, the Board makes the following Findings of Fact:

1.	The determination below corresponds with the January 28, 2025 plan of action report compiled by the Appellant.  The above report was utilized by the Board, the Appellant and the Providence Fire Marshals Office during the May 6, 2025 hearing on this matter.  Accordingly, the Board hereby incorporates the January 28, 2025 plan of action report as its initial findings of fact.  Any modification of the Boards findings relating to this report, such as correction of a deficiency by the Appellant, shall be noted herein.
2.	The building is an existing 3-story above grade building without a basement level, classified as an apartment (42 units) occupancy, consisting of approximately forty-four thousand eight hundred fifty-four (44,854) square feet (gross area) and originally built in 1989.
3.	The building is of Type V (000) construction, has a compliant fire alarm system with emergency forces notification and is provided with an approved (partial) automatic sprinkler system.
4.	There is no objection by the Providence Fire Marshals Office to the granting of the relief outlined herein.

CONCLUSIONS OF LAW AND
DETERMINATIONS ON VARIANCE REQUESTS

References to NFPA shall mean the National Fire Protection Association; references to the Rhode Island Fire Code [RIFC] shall mean NFPA 1, (2018 edition) as incorporated by reference and amended by 450-RICR-00-00-7; and, references to the Rhode Island Life Safety Code [RILSC] shall mean NFPA 101, (2018 edition) as incorporated by reference and amended by 450-RICR-00-00-8.

1.	The Board hereby grants the Appellant a variance from the provisions of RILSC section Table 7.2.2.2.1.1(b) by allowing the existing 34 staircase to the maintenance office to remain in use without modification based upon a structural hardship.

Any deficiency understood by the Board to have been corrected, which is not so corrected, shall be immediately corrected by the Appellant.  The term approved, as used herein, is understood to mean in accordance with the specific provisions related to the particular subject as are contained in this Code, or as approved in particular by the Authority Having Jurisdiction (State Fire Marshal, his or her designated Deputy State Fire Marshals and/or Assistant Deputy State Fire Marshals).

STATUS OF DECISION AND APPEAL RIGHTS

1.	This Decision constitutes a final order of the Fire Safety Code Board of Appeal and Review as set forth in RIGL section 42-35-12 and represents a comprehensive, integrated plan of fire safety for the above-captioned facility under the above-cited use or occupancy.  Accordingly, every variance granted is conditioned upon the Appellants timely and continued compliance with all of the directives of the Board.  Every variance granted is further conditioned upon the continued use or occupancy of this facility under the above-cited classification reviewed by the Board.  [See: Fire Safety Code [FSC] section 450-RICR-00-00-1.7.2(W)].
2.	Failure of the Appellant to initially comply with the full Decision of the Board, within the stated time frame, shall void all variances granted herein.  [See: FSC section 450-RICR-00-00-1.7.2(Y)].  In the event of complete, timely and continued compliance with the full Decision of the Board, the above-cited variances shall be deemed to have vested in the above-captioned facility.  As long as this facility is in continued compliance with the full Decision of the Board, the above-cited variances shall remain with this facility in the absence of any change in use or occupancy mandating review under a separate classification of the FSC or a revision of the above-cited classification.  [See: FSC section 450-RICR-00-00-1.7.2(Z)].
3.	Such changes in use or occupancy of this facility, or failure to continually comply with the Boards Decision shall void all variances granted under the above-cited use or occupancy.  If such change creates a new use or occupancy as outlined in RIGL section 23-28.1-6, all variances granted under the original use or occupancy are void and this facility shall be reviewed under the newly created use or occupancy.  [See:  FSC section 450-RICR-00-00-1.7.2(AA)].
4.	In accordance with RIGL section 23-28.3-5(e), any person who violates a final order of the Board may be subject to prosecution in the District Court with possible imprisonment for a term not exceeding one (1) year, or fined not more than one thousand dollars (1000) for each offense.
5.	In accordance with RIGL section 42-35-12, the Appellant may appeal the Boards Decision, within thirty (30) days of the mailing date of this Decision, by commencing an action against the State Fire Marshal in the Sixth Division of the District Court.  [See: RIGL section 23-28.3-6 and FSC section 450-RICR-00-00-1.7.2(S)].  Commencement of such an action does not operate as an automatic stay of this Decision [See: RIGL section 42-35-15(c)].
rhode island coat of arms A Rhode Island Government Web site